| Plan Review Notes For Permit 03100871 |
| Permit Number |
03100871 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-11-04 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | | | | 1) SHT A2 FLOOR PLAN, INDICATE THE LOCA- | | | TION OF THE ACCESSIBLE TOILET ROOM FOR | | | THE SOUND ADVISE STORE. 104.2.1 | | | 2) SHT A2 NO DRINKING FOUNTAINS SHOWN ON | | | FLOOR PLAN. 104.2.1 | | | 3) SHT A2 ACCESSIBLE TOILET ROOMS. PRO- | | | VIDE A DETAIL FOR ALL ACCESSIBLE TOILET | | | ROOMS PER SECTIONS 11-4.22, 11-4.16, | | | 11-4.19, AND 11-4.18 AND ALL SUBSECTIONS | | | 4) SHTS P1 & P2 WET VENT, ONLY THE FIX- | | | TURES WITHIN THE BATHROOM GROUPS SHALL | | | CONNECT TO THE WET-VENTED HORIZONTAL | | | BRANCH DRAIN. 909.1 THE DRINKING FOUNT- | | | AIN SHALL TIE IN DOWNSTREAM OF THE BATH- | | | ROOM FIXTURES. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|