2003-11-18 00:00:00DENIED:
 1.PLAN SHEET M-1 INDICATES OA LOUVER
 ON OUTSIDE WALL AND DOES NOT INDICATE
 ANY DUCTWORK TO MIX OA WITH THE A/C
 SYSTEM.PLEASE SHOW COMPLIANCE WITH
 ASHRAE 62-89 SECTION 6.1.3.2 & 6.1.3.3.
  
 2.PLEASE NOTE LOCATION OF OA.PLAN
 SHEETS A-1 & A-2 INDICATE OVERHEAD DOORS
 IN THE SAME AREA AS THE OA LOUVER.WILL
 THIS BE AN AREA FOR DELIVERIES & P/U?
 OA SHALL NOT BE LOCATED WHERE NOXIOUS
 CONTAMINANTS ARE PRESENT PER 2001 FBC(M)
 401.5.1.
  
 3.PLEASE NOTE THE HEIGHT REQUIREMENT
 FOR THE STAND FOR THE CONDENSING UNIT
 SHALL COMPLY WITH 2001 FBC 1511.7
 (SEE ATTACHED).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.