| Plan Review Notes For Permit 03100871 |
| Permit Number |
03100871 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-11-18 00:00:00 | DENIED: | | | 1.PLAN SHEET M-1 INDICATES OA LOUVER | | | ON OUTSIDE WALL AND DOES NOT INDICATE | | | ANY DUCTWORK TO MIX OA WITH THE A/C | | | SYSTEM.PLEASE SHOW COMPLIANCE WITH | | | ASHRAE 62-89 SECTION 6.1.3.2 & 6.1.3.3. | | | | | | 2.PLEASE NOTE LOCATION OF OA.PLAN | | | SHEETS A-1 & A-2 INDICATE OVERHEAD DOORS | | | IN THE SAME AREA AS THE OA LOUVER.WILL | | | THIS BE AN AREA FOR DELIVERIES & P/U? | | | OA SHALL NOT BE LOCATED WHERE NOXIOUS | | | CONTAMINANTS ARE PRESENT PER 2001 FBC(M) | | | 401.5.1. | | | | | | 3.PLEASE NOTE THE HEIGHT REQUIREMENT | | | FOR THE STAND FOR THE CONDENSING UNIT | | | SHALL COMPLY WITH 2001 FBC 1511.7 | | | (SEE ATTACHED). | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|