2003-10-22 00:00:00******** UNSAT ***********
  
 1)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%. 215.3,230.42,ETC.
  
 2)NOTE: PLEASE SHOW LOAD ON EXISTING
 MDP. PLANS DO SHOW DELETION OF EXSITING
 PANELS, BUT LOAD ON THOSE PANELS AND
 MDP IS UNCLEAR.
 215.5
  
 3)NOTE: PLEASE CLARIFY DISTANCE FOR
 TAPPED CONDUCTORS FOR A/C. PER 240.21
  
 4)NOTE: PLEASE CLARIFY, PLAN SHOWS A
 "KEY NOTE" #5 BELOW PANEL "A" AND KEY
 NOTES DO NOT HAVE A #5?
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 THAT MAY OR MAY NOT HAVE AN AFFEACT ON
 ELECTRICAL SHEETS.
 PLEASE BE SURE TO REMOVE ALL OLD/VOIDED
 SHEETSA AND INSERT NEW SHEETS INTO SETS
 FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  