| Plan Review Notes For Permit 03100871 |
| Permit Number |
03100871 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-10-22 00:00:00 | ******** UNSAT *********** | | | | | | 1)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS | | | AT 125%. 215.3,230.42,ETC. | | | | | | 2)NOTE: PLEASE SHOW LOAD ON EXISTING | | | MDP. PLANS DO SHOW DELETION OF EXSITING | | | PANELS, BUT LOAD ON THOSE PANELS AND | | | MDP IS UNCLEAR. | | | 215.5 | | | | | | 3)NOTE: PLEASE CLARIFY DISTANCE FOR | | | TAPPED CONDUCTORS FOR A/C. PER 240.21 | | | | | | 4)NOTE: PLEASE CLARIFY, PLAN SHOWS A | | | "KEY NOTE" #5 BELOW PANEL "A" AND KEY | | | NOTES DO NOT HAVE A #5? | | | | | | PLEASE SEE COMMENTS FROM OTHER REVIEWERS | | | THAT MAY OR MAY NOT HAVE AN AFFEACT ON | | | ELECTRICAL SHEETS. | | | PLEASE BE SURE TO REMOVE ALL OLD/VOIDED | | | SHEETSA AND INSERT NEW SHEETS INTO SETS | | | FOR REVIEW AND STAMPING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|