| 2003-12-01 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 03100871 |
| | ADD: 2275 PALM BEACH LAKES BLVD |
| | CONT: HALLMARK BUILDERS |
| | TEL: (561)512-5517 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | ACTION: DENIED |
| | |
| | 1) FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: OVERHEAD DOOR |
| | |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. |
| | |
| | 2) WHAT TYPE OF OCCUPANCY WILL THE NEW |
| | AREA BE USED FOR? THERE IS NEW PROPOSED |
| | 10'X10' DOORS BUT BALLARDS TO STOP |
| | AUTO ENTRY? |
| | |
| | 3) SHEET A-3 INDICATES A 2HR WALL DETAIL |
| | U-411, THE DETAIL NEGLETES TO INDICATE |
| | THE REQUIRED INSULATION(3, 3A OR 3B). |
| | |
| | 4) PROVIDE THE TYPE OF SEALENT SYSTEM TO |
| | BE USED TO PROVIDE A 2 HR RATING FOR THE |
| | WALL METAL ROOF DECK ASSEMBLY. |
| | |
| | BUILDING PLAN REVIEW |