| 2003-12-05 00:00:00 | ************** UNSAT ************* | | | | | | 1)NOTE: PLEASE SUBMIT PLANS DRAWN TO | | | MEET 104.2 OF THE FAC. BOTH SETS OF PLAN | | | -S NEED TO VERY CLEAR AND READABLE. | | | | | | 2)NOTE: PLEASE CORRELATE BOTH SETS. MANY | | | ITEMS ARE NOT THE SAME ON EACT SET. | | | | | | 3)NOTE: PLEASE CLARIFY MEANS OF EGRESS | | | LIGHTING CONTROL FOR ROOMS. APPEARS TO | | | SHOW FANS? OR ARE THESE FANS/LT COMBO? | | | 210.70 | | | | | | 4)NOTE: PLEASE LIST REQ'D ARC FAULT | | | PROTECTED CIRCUITS ON PANELSCEDULE. | | | 210.12 | | | | | | 5)NOTE: PLEASE SHOW A/C LOCATIONS AND | | | REQ'D DISC'S PER 440.11. SHOW RECEPT/GFI | | | PER 210.63 AND IF AHU IS IN ATTIC.210.70 | | | LT. | | | | | | 6)NOTE: PLEASE SHOW ALL RECEPTS SERVING | | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- | | | ED. PER 210.8A-6 | | | | | | 7)NOTE: PLEASE CORRELATE LOADS SHOWN ON | | | PANEL SCHEDULE AND ON LOAD CALCAULATIONS | | | | | | PLEASE ATTACH AND MAKE TWO COMPLETE SETS | | | FOR REVIEW. PLEASE DO THIS WITH PLANS | | | FOR ALL TRADES. | | | PLEASESUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|