Plan Review Notes
Plan Review Notes For Permit 03100781
Permit Number 03100781
Review Stop E
Sequence Number 2
Notes
Date Text
2003-12-05 00:00:00************** UNSAT *************
  
 1)NOTE: PLEASE SUBMIT PLANS DRAWN TO
 MEET 104.2 OF THE FAC. BOTH SETS OF PLAN
 -S NEED TO VERY CLEAR AND READABLE.
  
 2)NOTE: PLEASE CORRELATE BOTH SETS. MANY
 ITEMS ARE NOT THE SAME ON EACT SET.
  
 3)NOTE: PLEASE CLARIFY MEANS OF EGRESS
 LIGHTING CONTROL FOR ROOMS. APPEARS TO
 SHOW FANS? OR ARE THESE FANS/LT COMBO?
 210.70
  
 4)NOTE: PLEASE LIST REQ'D ARC FAULT
 PROTECTED CIRCUITS ON PANELSCEDULE.
 210.12
  
 5)NOTE: PLEASE SHOW A/C LOCATIONS AND
 REQ'D DISC'S PER 440.11. SHOW RECEPT/GFI
 PER 210.63 AND IF AHU IS IN ATTIC.210.70
 LT.
  
 6)NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 ED. PER 210.8A-6
  
 7)NOTE: PLEASE CORRELATE LOADS SHOWN ON
 PANEL SCHEDULE AND ON LOAD CALCAULATIONS
  
 PLEASE ATTACH AND MAKE TWO COMPLETE SETS
 FOR REVIEW. PLEASE DO THIS WITH PLANS
 FOR ALL TRADES.
 PLEASESUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  