| 2003-12-10 00:00:00 | ***CORRECTIONS*** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)ADDITIONAL PERMITS REQUIRED. |
| | |
| | 2.)SEE PREVIOUS LIST, PROVIDE A |
| | HURRICANE SHUTTER INSTALLATION SCHEDULE. |
| | IF THIS IS NOT SUBMITTED, A SEPARATE |
| | PERMIT FOR HURRICANE SHUTTERS WILL BE |
| | REQUIRED. |
| | |
| | 3.)OLD PLANS ARE NOT IN THE PACKAGE. |
| | THE DEMO OF THE STAIRS IS NOT ON THIS |
| | PLAN. |
| | |
| | 4.)EFFECTIVE OCTOBER 1, 2003, |
| | STATEWIDE OR SITE SPECIFIC PRODUCT |
| | APPROVAL REQUIRED FOR WINDOWS, DOORS, |
| | ROOF, SHUTTERS.SEE WWW.FLORIDABUILDING |
| | .ORG FOR MORE INFORMATION.PERMIT WILL |
| | BE ISSUED WITH A PROVISO TO PROVIDE |
| | STATEWIDE OR SITE SPECIFIC BEFORE |
| | INSTALLATION. |
| | |
| | 5.)ARE ALL OF THE WINDOWS BEING REPLAC |
| | ED AS SHOWN ON "PROPOSED"?IF THEY |
| | ARE, ADD TO THE PERMIT APPLICATION. |
| | |
| | 6.)SEE PREVIOUS LIST; SHOW BEDROOMS |
| | ON THE PLAN SHOWING COMPLIANCE WITH |
| | FBC1005.4, EMERGENCY EGRESS. |
| | |
| | 7.)THE LANDING MUST BE AT LEAST THE |
| | WIDTH OF THE DOOR, FBC1007.4. |
| | |
| | 8.)THE STAIR DOES NOT COMPLY WITH |
| | FBC1007.3.1, TREADS APPEAR TO BE 13", |
| | RISER APPEARS TO BE 7", 2 RISERS + 1 |
| | TREAD IS TO BE 24"-25" (EXCLUSIVE OF |
| | NOSING, INDICATE NOSING DISTANCE ON |
| | PLAN IF APPLICABLE). |
| | |
| | 9.)SEE PREVIOUS LIST, #14, FRONT DOOR |
| | TO HAVE A CLEAR OPENING OF 32".A |
| | 32" DOOR DOES NOT COMPLY. |
| | |
| | 10.) SEE PREVIOUS LIST, ITEM #20, |
| | THE LANDING DOES NOT COMPLY WITH FBC |
| | 1004.7.2, LANDING SHALL HAVE A MINIMUM D |
| | DIMENSION MEASURED IN THE DIRECTION OF |
| | TRAVEL EQUAL TO THE WIDTH OF THE |
| | STAIRWAY.SEE EXCEPTION (48"). |
| | |
| | 11.)THE RAILING DETAIL DOES NOT SHOW |
| | THE HEIGHT.SHOW COMPLIANCE WITH FBC |
| | 1015.3, OPENINGS, SEE ATTACHED. |
| | |
| | 12.)PROVIDE A STRUCTURAL DETAIL OF THE |
| | ROOF OVERHANG.IT SHOWS LUMBER AND |
| | REDHEADS; NO CONNECTORS, SHEATHING,ROOF. |