Plan Review Notes
Plan Review Notes For Permit 03100781
Permit Number 03100781
Review Stop M
Sequence Number 1
Notes
Date Text
2003-10-29 00:00:00DENIED:
 1.PROVIDE COMPLETED FORM 600C AS PER
 2001 FBC CHAPTER 13 SECTION 600.1.C.
  
 2.PLEASE NOTE, NO PLANS SUBMITTED FOR
 REVIEW AND WILL BE SUBJECT TO FIELD
 INSPECTORS APPROVAL.
  
 3.RETURN AIR REQUIRED FROM ROOMS WITH
 CLOSING DOORS (EXAMPLE: BEDROOMS).
 RETURN AIR TO COMPLY WITH REVISION TO
 THE 2001 FBC(M) 601.4 EFFECTIVE 6-30-03:
 BALANCED AIR RETURN - RETURN/TRANSFER
 SHALL BE 1 1/2 TIMES THE CROSS SECTIONAL
 AREA (SQ INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM ITS SERVING & THE
 DOOR HAVING AN UNRESTRICTED 1" UNDERCUT.
  
 ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED.
  
 4.OVERFLOW PROTECTION REQUIRED AS PER
 2001 FBC(M) 307.2.3, AUXILIARY DRAIN PAN
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.