2003-10-23 00:00:00DENIED:
 RETURN AIR TO THE BEDROOMS AND CLUB
 ROOM ARE NOT SIZED CORRECTLY.PLEASE
 REVISE PLANS TO COMPLY WITH THE
 REVISION TO THE2001 FBC(M) 601.4,
 EFFECTIVE JUNE 30, 2003.
  