| Plan Review Notes For Permit 03100751 |
| Permit Number |
03100751 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-10-22 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SEE FAC 61G1-16.004 AND | | | INCLUDE ALL LICENSE INFORMATION ON TITLE | | | BLOCK. PER FS 471 | | | | | | 2)NOTE: PLEASE SEE THAT WE ARE NOW UNDER | | | THE 2002 NEC AND REQUIREMENTS FOR 210.12 | | | HAVE CHANGED. PLANS MENTIONS RECEPTS. | | | THIS IS NO LONGER THE CASE. | | | | | | 3)NOTE: PLEASE SEE RISER, SHOWS A METER/ | | | MAIN COMBO AND STILL SHOWS SUB PANEL "A" | | | AS MCB. THIS IS PERMITTED, HOWEVER IF | | | SHOWN, THEN A MCB WILL BE REQ'D TO BE | | | INSTALLED. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|