| Date |
Text |
| 2004-02-05 00:00:00 | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CIRCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | PLEASE NOTE ON PLAN. |
| | |
| | 2} A RECEPTACLE IS REQUIRED ON THE WALL |
| | BETWEEN THE DOORS IN THE NORTH EAST |
| | CORNER IN THE BEDROOM PER 210.52(A)(2). |
| | |
| | 3} SMOKE DETECTORS ARE REQUIRED PER |
| | 8-1.4.1.6.2 NFPA-72,AND WIRED PER |
| | 905.2.5 FBC. |
| | |
| | 4} CHANGES TO THE PLAN MUST BE DONE BY |
| | THE DESIGNER OF RECORD (ARCHITECT). |
| | |
| | 5} PLEASE PROVIDE A CALCULATION |
| | INCLUDI-NG ALL ADDED LOADS IMPOSED,ALL |
| | EXISTING LOADS AND THE EXISTING OR |
| | PROPOSED |
| | SERVICE SPECIFICATIONS PER 215.15.ALSO |
| | SEE 220.3(A)(4) REGARDING RECESSED |
| | LUMINAIRS. |
| | |
| | 6} PLEASE NOTE, ALL PLANS DRAWN |
| | BY AN ARCHITECT/ENGINEER CONTAIN- |
| | -ING A TITLE BLOCK: MUST BE SIGNED, |
| | DATED AND SEALED BY THAT ARCH/ENG. |
| | PER FS 481.221 471.025 |
| | FAC 61G15-23.002, 61G1-16.004 |
| | |
| | 7} PLEASE NOTE THAT A SEPARATE |
| | ELECTRICAL PERMIT IS REQUIRED FOR THIS |
| | WORK. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |
| | [email protected] |
| | FAX/:561/659-8026 |