Plan Review Notes
Plan Review Notes For Permit 03100703
Permit Number 03100703
Review Stop E
Sequence Number 1
Notes
Date Text
2004-02-05 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 PLEASE NOTE ON PLAN.
  
 2} A RECEPTACLE IS REQUIRED ON THE WALL
 BETWEEN THE DOORS IN THE NORTH EAST
 CORNER IN THE BEDROOM PER 210.52(A)(2).
  
 3} SMOKE DETECTORS ARE REQUIRED PER
 8-1.4.1.6.2 NFPA-72,AND WIRED PER
 905.2.5 FBC.
  
 4} CHANGES TO THE PLAN MUST BE DONE BY
 THE DESIGNER OF RECORD (ARCHITECT).
  
 5} PLEASE PROVIDE A CALCULATION
 INCLUDI-NG ALL ADDED LOADS IMPOSED,ALL
 EXISTING LOADS AND THE EXISTING OR
 PROPOSED
 SERVICE SPECIFICATIONS PER 215.15.ALSO
 SEE 220.3(A)(4) REGARDING RECESSED
 LUMINAIRS.
  
 6} PLEASE NOTE, ALL PLANS DRAWN
 BY AN ARCHITECT/ENGINEER CONTAIN-
 -ING A TITLE BLOCK: MUST BE SIGNED,
 DATED AND SEALED BY THAT ARCH/ENG.
 PER FS 481.221 471.025
 FAC 61G15-23.002, 61G1-16.004
  
 7} PLEASE NOTE THAT A SEPARATE
 ELECTRICAL PERMIT IS REQUIRED FOR THIS
 WORK.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved