2003-11-09 00:00:00*****CORRECTIONS*****
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 561-805-6724
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.13.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025
  
 3.)THE SURVEY SHOWS A SCREEN
 ENCLOSURE.YOU ARE BUILDING THROUGH
 HALF OF IT.ARE YOU DEMOLISHING THE
 ENTIRE SCREEN ROOM?SHOW ON THE PLAN.
  
 4.)THE NAME AND SIGNATURE TO THE
 PERSON RESPONSIBLE FOR THE DESIGN IS
 REQUIRED TO BE ON THE PLAN (EACH SHEET),
 FBC104.2.
  
 5.)SEPARATE PERMITS REQUIRED.
  
 6.)SHOW AREA CALCULATIONS ON THE PLAN,
 EXISTING, PROPOSED, NEW TOTAL. ADDITIONS
 OF OVER 25% OF EXISTING BUILDING AREA
 ARE REQUIRED TO COMPLY WITH FBC3401.7.2
 (SMOKE DETECTORS AND GFCIS IN EXISTING
 HOUSE), SHOW COMPLIANCE ON THE PLAN IF
 APPLICABLE.
  
 7.)ENERGY CALCS REQUIRED, FBC13-103.1.
 2.SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC.
  
 8.)AN EXISTING SLAB IS IN THE AREA
 WHERE YOU ARE PROPOSING AN ADDITION.IT
 IS NOT SHOWN OR ADDRESSED ON THE PLAN.
 PROVIDE A FOUNDATION PLAN.
  
 9.)THE WALL SECTION SHOWS A PITCHED
 ROOF, THE ELEVATIONS SHOW A FLAT ROOF.
 IF IT IS PITCHED, SPECIFY THE PITCH.
 THE WALL SECTION MUST MATCH THE
 ELEVATIONS.
  
 10.) ALL DRAWINGS ARE TO BE TO SCALE
 FBC104.2.SHOW SCALE ON THE PLAN.
  
 11.)ADDITIONAL FEES (RADON), $5.12,
 SEE ATTACHED BZ233266.
  
 12.)THE ELEVATIONS DO NOT MATCH THE
 SITE/FLOOR PLANS, APPEARS THAT EAST AND
 WEST ARE LABELED INCORRECTLY.
  
 13.)MARK ROOMS BY USE (EX: BEDROOM,
 KITCHEN).
  
 14.)ON THE EXISTING FLOOR PLAN, YOU
 ARE BLOCKING ALL WINDOWS AND DOORS TO A
 ROOM WHICH APPEARS TO BE A BEDROOM.
 BEDROOMS ARE REQUIRED TO HAVE EMERGENCY
 EGRESS TO COMPLY WITH FBC1005.4.
  
 15.)IMPACT PROTECTION REQUIRED FOR
 GLAZING, FBC1606.1.7.PROVIDE A
 HURRICANE SHUTTER INSTALLATION SCHEDULE
 PER WPB POLICY.
  
 16.)THE WALL SECTION IS TO INCLUDE
 ASSEMBLY AND MATERIALS.IT REFERS TO A
 ROOF PLAN WHICH IS NOT ON THE PLAN.
 PROVIDE A ROOF FRAMING PLAN.SHOW
 ALL CONNECTIONS.
  
 17.)THE BOTTOM OF THE FOOTER IS
 REQUIRED TO BE A MINIMUM OF 12" BELOW
 GRADE, FBC1804.1.3.
  
 18.)THE CONNECTOR SPECIFIED "SIMPSON
 ETA16" IS NOT IN THE SIMPSON 2003
 CATALOG.
  
 19.)THE FRAMING DETAIL AT THE WINDOW
 SPECIFIES A HUGHES STRAP, NO LONGER IN
 BUSINESS.IT ALSO SPECIFIES "USP RTPGA
 824", NOT IN THE USP 2003 CATALOG.
 REVISE.
  
 20.)THE WINDOW/DOOR BUCK DETAIL IS FOR
 MASONRY, THE WALL SECTION IS WOOD FRAME.
 CLARIFY.
  
 21.)PROVIDE DESIGN INFORMATION ON THE
 PLAN FBC1606.1.7, 2003 AMENDMENT.
  
 22.)SMOKE DETECTORS REQUIRED FOR
 BEDROOMS, FBC905.2.2.
  
 23.)PROVIDE A FOUNDATION PLAN.
  
 24.)STATEWIDE OR LOCAL PRODUCT
 APPROVALS ARE REQUIRED.ANY PRODUCT
 APPROVALS NOT SUBMITTED AT THE TIME OF
 PERMIT ISSUANCE WILL NOT INCLUDE THOSE
 ITEMS AS PART OF THIS PERMIT AND WILL
 REQUIRE A SEPARATE APPLICATION WITH
 ADDITIONAL FEES.THIS DOES NOT APPLY
 TO STRUCTURAL COMPONENTS, WHICH ARE
 REQUIRED FOR THIS PERMIT.SEE THE
 DCA WEBSITE FOR MORE INFORMATION:
  
 WWW.DCA.STATE.FL.US/FHCD/FBC/COMMITTEES/
 PRODUCT_APPROVAL/1_PRODUCT_APPROVAL.HTM
  
 FAC9B-72.050, EFFECTIVE OCTOBER 1, 2003