Plan Review Notes
Plan Review Notes For Permit 03100700
Permit Number 03100700
Review Stop B
Sequence Number 1
Notes
Date Text
2003-10-30 00:00:00****CORRECTIONS*****
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)PLANS WITH THE ENGINEER'S TITLE
 BLOCK MUST BE SEALED FS471.025.
  
 2.)INCLUDE ALL INFORMATION IN REGARDS
 TO DESIGN AS REQUIRED BY FBC1606.1.7,
 2003 AMENDMENT (STEEL BUILDING PLAN).
  
 3.)THE GARAGE DOOR DRAWINGS ARE NOT
 LEGIBLE.IT APPEARS THAT THERE ARE
 SPECIFICATIONS FOR THE DOOR TO BE
 INSTALLED IN EITHER WOOD OR MASONRY,
 BUT NOT STEEL.ADDRESS.
  
 4.)STATEWIDE OR LOCAL PRODUCT
 APPROVAL IS REQUIRED FOR THE PANEL
 WALLS, ROOF, GARAGE DOOR, AND ALL
 STRUCTURAL COMPONENTS.FOR MORE
 INFORMATION, GO TO THE DCA WEBSITE AT:
 WWW.DCA.STATE.FL.US/FHCD/FBC/COMMITTEES/
 PRODUCT_APPROVAL/1_PRODUCT_APPROVAL.HTM
  
 5.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 6.)THE COLUMNS AND FENCE ARE NOT A
 PART OF THIS PERMIT PER ZONING (SEE NOTE
 ON THE PLAN).REMOVE THEM FROM THE
 PLAN.FYI, THE FOOTING CANNOT ENCROACH
 THE PROPERTY.