2004-12-28 00:00:00REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
 CITY CODE
  
 1) SHT 1 SANITARY RISER DIAGRAM DOES
 NOT
 MEET THE CODE REQUIREMENTS.
 A) WASH MACHINE AND LAUNDRY SINK SHALL
 DISCHARGE DOWNSTREAM OF THE HORIZONTAL
 WET-VENT FOR THE BATHROOM FIXTURES.
 SECTION 909.1
 B) ROOF DRAIN SHALL NOT DRAIN INTO THE
 SANITARY SYSTEM PER CITY CODE SECTION
 90-125(5)
  
  
  
 REVIEW BY KEN STEVENS