| Plan Review Notes For Permit 03100662 |
| Permit Number |
03100662 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2003-12-16 00:00:00 | ************ UNSAT *************** | | | | | | 1)NOTE: PLEASE SEE 600.5. REQ'S SIGN | | | CIRCUIT. NO OTHER LOADS ARE PERMITTED | | | ON CIRCUIT. | | | | | | 2)NOTE: PLEASE SEE LOAD SHOWN FOR WASHER | | | /DRYER COMBO. PLEASE VERIFY LOAD. NEC | | | 220.18 REQ'S A MIN OF 5KW. | | | | | | 3)NOTE: PLEASE ALSO SEE LOAD SHOWN FOR | | | COMBO DRYER/WASHER IS 4KW AND IS SHOWN | | | ON A 1-POLE 20A BRKR. | | | | | | 4)NOTE: PLEASE SEE LOADFOR RANGE | | | SHOWN AT 14KW AND ON A 2P-50A BRKR. | | | LOAD EXCEEDS RATING OF BRKR. | | | | | | 5)NOTE: PLEASE SEE LOAD FOR AHU'S. | | | LOADS SHOWN AT 10.2KW. PLEASE VERIFY | | | MAX OCP. SHOWS 2-P-70A. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|