| 2003-11-04 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | |
| | 1) THESE SPACES WERE RESIDENTIAL OCCU- |
| | PANCIES. AS A CHANGE OF OCCUPANCY FROM |
| | RESIDENTIAL TO COMMERCIAL, SECTION |
| | 3402.2.2.1 THE BUILDING, ELECTRICAL, GAS |
| | MECHANICAL AND PLUMBING SYSTEMS SHALL BE |
| | MADE TO COMFORM TO THE INTENT OF THE |
| | TECHNICAL CODES AS REQUIRED BY THE BLDG. |
| | OFFICIAL. |
| | 2) IF BATHING FACILITIES ARE PROVIDED ON |
| | A SITE THEN EACH SUCH PUBLIC OR COMMON |
| | USE BATHING FACILITY SHALL COMPLY WITH |
| | 11-4.23.SECTION 11-4.1.2(6) |
| | SUBMIT DETAIL FOR FOR BOTH THE TOILET |
| | ROOM AND THE BATHING SHOWING COMPLIANCE |
| | WITH SECTIONS 11-4.22, & 11-4.23 AND |
| | ALL SUBSECTIONS. SHOW COMPLIANCE WITH |
| | 11-4.16, 11-4.19, & 11-4.20 AND ALL SUB- |
| | SECTIONS. SEE FIGURES 28, 29, 32, 33, & |
| | 34. |
| | 3) BREAKROOM SINK SHALL COMPLY WITH |
| | SECTION 11-4.24 AND ALL SUBSECTIONS. |
| | PROVIDE DETAILS. |
| | 4) BATHTUB THAT WILL BE COVERED SHALL |
| | HAVE THE WASTE AND OVERFLOW SEALED TO |
| | KEEP SEWER GASSES FROM ESCAPING. |
| | 5) ALL CAPPED WATER AND SANITARY LINES |
| | SHALL BE INSPECTED PRIOR TO COVERING. |
| | |