| 2004-05-05 00:00:00 | ************* UNSAT ************** |
| | |
| | 1)NOTE: PLEASE SEE FAC 61G15-23.002, |
| | FS 471.023. PLEASE SEE MISSING REQ'D |
| | LICENSE #'S ON TITLE BLOCKS. THIS IS |
| | REQ'D FOR ALL TRADES WEATHER OR NOT |
| | COMMENT IS MADE FROM OTHER REVIEWERS |
| | THIS HAS BEEN REQUESTED ON PREVIOUS |
| | REVIEW. |
| | THE STATE DOES NOT HAVE ANY LISTING OF |
| | A REQ'D LICENSE / CA#?? |
| | PLEASE VERIFY LICENSING W/ FBPE'S, DBPR. |
| | |
| | |
| | 2)NOTE: PLEASE SEE AN "ALUMINUM" EQUIP- |
| | -MENT GROUNDING CONDUCTOR HAS NOW BEEN |
| | ADDED. PLEASE SEE ALUM GRNDING CONDUCTOR |
| | -S ARE NOT PERMITTED. |
| | |
| | 3)NOTE: PLEASE CORRELATE RISER DIAGRAM, |
| | PANEL SCHEDULE AND LOAD CALCULATIONS. |
| | RISER SHOWS 200A SERVICE ALONG WITH |
| | PANEL SCHEDULE, YET PANEL SCHEDULE |
| | ALSO INDICATES A 150 MCB???? |
| | |
| | 4)NOTE: PLEASE PROVIDE LOAD CALCULATIONS |
| | TO MEET NEC 220. |
| | |
| | 5)NOTE: PLEASE CORRELATE LOAD CALCULAT- |
| | -IONS WITH PANEL SCHEDULE. THERE ARE |
| | MANY ITEMS THAT DO NOT CORRELATE. |
| | PLEASE SEE ONE SET REDLINED. |
| | |
| | 6)NOTE: PLEASE SEE 220.18 FOR MIN 5KW |
| | FOR DRYER. |
| | |
| | 7)NOTE: PLEASE SEE OCP SHOWN FOR AHU'S |
| | 7.5KW W/ 60A BRKRS. PLEASE VERIFY OCP. |
| | TOO HIGH. |
| | |
| | 8)NOTE: PLEASE SEE 110.26, DISC FOR A/C |
| | UNIT DOES NOT MEET ABOVE. |
| | |
| | 9)NOTE: PLEASE SEE WALKWAY/HALL BETWEEN |
| | NEW AND ADDITION. MEANS OF EGRESS |
| | CONTROL FOR LTS. 210.70 FROM MAIN HOUSE. |
| | |
| | 10)NOTE:PLEASE SEE NFPA-72 8-1.4.2, NO |
| | SD'S TO BE W/IN 3' FROM BATH DOOR. |
| | |
| | 11)NOTE: PLEASE SEE PREVIOUS COMMENT |
| | ABOUT CHAPTER 34 FBC. 3401.7.2.6 |
| | SHOW EXSITING LAYOUT OF EXIST HOUSE, |
| | ITEMS MUST BE SHOWN FOR BRING UP TO |
| | 2002 NEC. |
| | BLDG IS OVER 50%. |
| | |
| | 12)NOTE: PLEASE SHOW CONDUCTORS AND |
| | CONDUIT SIZE FROM MAIN DISC TO PANEL. |
| | 215.5, 310.15B6 |
| | |
| | 13)NOTE: PLEASE SUBMIT AIC RATING FOR |
| | NEW MAIN. 110.9,215.5 |
| | |
| | PLEASE SEE COPY OF FS 553.80(2)(B) |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |