Plan Review Notes
Plan Review Notes For Permit 03100659
Permit Number 03100659
Review Stop E
Sequence Number 2
Notes
Date Text
2004-02-10 00:00:00************** UNSAT *****************
  
 **** PLEASE SEE ZONING NOTES, AS THEY
 WILL HAVE A DIRECT AFFECT ON ELETCRICAL,
 MECHANICAL, AND PLUMB PLANS***********
  
 *PLEASE SEE ELECTRICAL NOTE FROM FRIST
 REVIEW. PLEASE SEE MOST NOTES STILL
 NEED TO BE ADDRESSED.
  
 1)NOTE: PLEASE SEE 230.2,230.70,230.72,
 TWO SERVICES ARE NOT PERMITTED AND MAINS
 MUST BE GROUPED PER 230.72
  
 2)NOTE: PLEASE SHOW LOCATIONS OF ALL
 ELECTRICAL SERVICE EQUIPMENT ON PLANS.
  
 3)NOTE: PLANS SHOW TWO SEPARATE RISERS,
 HOWEVER THESE ITEMS ARE NOT SHOWN ON
 PLANS? IF INDEED THIS IS ONLY ONE SERV-
 -ICE, PLEASE CORRELATE LOAD CALCS.
 PLEASE SEE THAT A/C SYSTEMS ARE SHOWN ON
 EACH SERVICE AND DO NOT COME FROM ONE.
 SMALL APPL, DRYERS, WASHER ETC.
 PANEL SCHEDULES WERE NOT SUBMITTED AS
 REQUESTED ON FIRST REVIEW, UNABLE TO
 VERIFY.
  
 4)NOTE: PLEASE SEE 310.15B6/310.16 FOR
 SIZING OF SERVICE ENTRANCE CONDUCTORS
 AND FEEDERS. PLANS SHOW 1/0'S, THESE
 ARE NOT OF SUFF SIZE FOR 200A SERVICE.
 RISER IS MISSING CONDUCTORS FROM MAIN(S)
 TO PANELS.
 PLEASE ALSO SEE MISSING EQUIPMENT GROUND
 -ING CONDUCTOR FROM MAIN TO PANEL. PER
 250.110,250.24, SIZE PER 250.122
  
 5)NOTE: PLEASE SEE MISSING COLD WATER
 PIPE TO BE PART OF THE GROUNDING ELECT-
 -RODE SYSTEM. 250.50
  
 6)NOTE: PLEASE SEE RISER, INDICATES
 MAIN, YET 200A PANEL IS ALSO SHOWN AS
 MCB? PLEASE NOTE, THIS IS PERMITTED,
 HOWEVER NOT REQUIRED. IF PLANS SHOW,
 THEN THEY WILL BE REQ'D TO BE INSTALLED,
 UNLESS PLANS ARE REVISED.
  
 7)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
 MISSING SOME.
 SD'S ARE ALSO REQ'D TO BE A MIN OF 3'
 FROM BATHROOM DOORS AND KITCHENS. SD'S
 ARE ALSO NOT PEMITTED IN KITCHENS.
  
 8)NOTE: PLEASE SEE COMMENTS FROM FIST
 REVIEW, PANEL SCHEDULE(S)OCP,AWG, ETC
 ALONG WITH ALL MIN REQ'D DEDICATED
 CIRCUITS MUST BE SUBMITTED. 210.52D,
 210.11C3,210.11, 210.12ETC.
  
 9)NOTE: PLEASE SHOW/INDICATE ALL ROOM
 DESIGNATIONS ON ELECTRICAL PLANS. 1ST
 REVIEW.
  
 10)NOTE: PLEASE SEE FAC 61G15-23.002,
 FS 471.023. PLEASE INCLUDE ALL INFORMAT-
 -ION AS REQUIRED FOR TITLE BLOCK.
 PLEASE INCLUDE ALL LICENSE #'S.
 PLEASE SEE ADDRESS DOES NOT CORRELATE
 WITH FILE OF ACTUAL ADDRESS. PLANS SHOW
 257 AND PROPERTY IS LISTED AS 253.
  
 11)NOTE: PLEASE SEE COPY OF FS 553.80(2)
 (B) WITH RESPECT TO DESIGN PROFESSIONAL.
  
 12)NOTE: UNABLE TO DUE A COMPLETE REVIEW
 FOR CODE COMPLIANCE TO 2002NEC DUE TO
 MISSING REQUIRED INFORMATION.
  
 13)NOTE: PLEASE SEE FBC CHAPTER 34 FOR
 ADDITIONS TO EXSITNG BLDGS.
 PLEASE SEE THAT MORE THAN 25% IS BEING
 ADDED AND WILL REQUIRE EXISTING ELECTRIC
 -AL TO BE UPGRADED TO MEET 2002 NEC
 PLEASE PROVIDE PLANS/ LAYOUT FOR EXSIT-
 -ING ELECTRICAL AND LOCATION OF ALL
 DEVICES. PLEASE ALSO SEE THAT SD'S WILL
 BE REQUIREDFOR EXISTING, DEDICATED
 CIRCUITS, GFI'S, ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]