| 2004-02-10 00:00:00 | ************** UNSAT ***************** |
| | |
| | **** PLEASE SEE ZONING NOTES, AS THEY |
| | WILL HAVE A DIRECT AFFECT ON ELETCRICAL, |
| | MECHANICAL, AND PLUMB PLANS*********** |
| | |
| | *PLEASE SEE ELECTRICAL NOTE FROM FRIST |
| | REVIEW. PLEASE SEE MOST NOTES STILL |
| | NEED TO BE ADDRESSED. |
| | |
| | 1)NOTE: PLEASE SEE 230.2,230.70,230.72, |
| | TWO SERVICES ARE NOT PERMITTED AND MAINS |
| | MUST BE GROUPED PER 230.72 |
| | |
| | 2)NOTE: PLEASE SHOW LOCATIONS OF ALL |
| | ELECTRICAL SERVICE EQUIPMENT ON PLANS. |
| | |
| | 3)NOTE: PLANS SHOW TWO SEPARATE RISERS, |
| | HOWEVER THESE ITEMS ARE NOT SHOWN ON |
| | PLANS? IF INDEED THIS IS ONLY ONE SERV- |
| | -ICE, PLEASE CORRELATE LOAD CALCS. |
| | PLEASE SEE THAT A/C SYSTEMS ARE SHOWN ON |
| | EACH SERVICE AND DO NOT COME FROM ONE. |
| | SMALL APPL, DRYERS, WASHER ETC. |
| | PANEL SCHEDULES WERE NOT SUBMITTED AS |
| | REQUESTED ON FIRST REVIEW, UNABLE TO |
| | VERIFY. |
| | |
| | 4)NOTE: PLEASE SEE 310.15B6/310.16 FOR |
| | SIZING OF SERVICE ENTRANCE CONDUCTORS |
| | AND FEEDERS. PLANS SHOW 1/0'S, THESE |
| | ARE NOT OF SUFF SIZE FOR 200A SERVICE. |
| | RISER IS MISSING CONDUCTORS FROM MAIN(S) |
| | TO PANELS. |
| | PLEASE ALSO SEE MISSING EQUIPMENT GROUND |
| | -ING CONDUCTOR FROM MAIN TO PANEL. PER |
| | 250.110,250.24, SIZE PER 250.122 |
| | |
| | 5)NOTE: PLEASE SEE MISSING COLD WATER |
| | PIPE TO BE PART OF THE GROUNDING ELECT- |
| | -RODE SYSTEM. 250.50 |
| | |
| | 6)NOTE: PLEASE SEE RISER, INDICATES |
| | MAIN, YET 200A PANEL IS ALSO SHOWN AS |
| | MCB? PLEASE NOTE, THIS IS PERMITTED, |
| | HOWEVER NOT REQUIRED. IF PLANS SHOW, |
| | THEN THEY WILL BE REQ'D TO BE INSTALLED, |
| | UNLESS PLANS ARE REVISED. |
| | |
| | 7)NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | MISSING SOME. |
| | SD'S ARE ALSO REQ'D TO BE A MIN OF 3' |
| | FROM BATHROOM DOORS AND KITCHENS. SD'S |
| | ARE ALSO NOT PEMITTED IN KITCHENS. |
| | |
| | 8)NOTE: PLEASE SEE COMMENTS FROM FIST |
| | REVIEW, PANEL SCHEDULE(S)OCP,AWG, ETC |
| | ALONG WITH ALL MIN REQ'D DEDICATED |
| | CIRCUITS MUST BE SUBMITTED. 210.52D, |
| | 210.11C3,210.11, 210.12ETC. |
| | |
| | 9)NOTE: PLEASE SHOW/INDICATE ALL ROOM |
| | DESIGNATIONS ON ELECTRICAL PLANS. 1ST |
| | REVIEW. |
| | |
| | 10)NOTE: PLEASE SEE FAC 61G15-23.002, |
| | FS 471.023. PLEASE INCLUDE ALL INFORMAT- |
| | -ION AS REQUIRED FOR TITLE BLOCK. |
| | PLEASE INCLUDE ALL LICENSE #'S. |
| | PLEASE SEE ADDRESS DOES NOT CORRELATE |
| | WITH FILE OF ACTUAL ADDRESS. PLANS SHOW |
| | 257 AND PROPERTY IS LISTED AS 253. |
| | |
| | 11)NOTE: PLEASE SEE COPY OF FS 553.80(2) |
| | (B) WITH RESPECT TO DESIGN PROFESSIONAL. |
| | |
| | 12)NOTE: UNABLE TO DUE A COMPLETE REVIEW |
| | FOR CODE COMPLIANCE TO 2002NEC DUE TO |
| | MISSING REQUIRED INFORMATION. |
| | |
| | 13)NOTE: PLEASE SEE FBC CHAPTER 34 FOR |
| | ADDITIONS TO EXSITNG BLDGS. |
| | PLEASE SEE THAT MORE THAN 25% IS BEING |
| | ADDED AND WILL REQUIRE EXISTING ELECTRIC |
| | -AL TO BE UPGRADED TO MEET 2002 NEC |
| | PLEASE PROVIDE PLANS/ LAYOUT FOR EXSIT- |
| | -ING ELECTRICAL AND LOCATION OF ALL |
| | DEVICES. PLEASE ALSO SEE THAT SD'S WILL |
| | BE REQUIREDFOR EXISTING, DEDICATED |
| | CIRCUITS, GFI'S, ETC. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |