Plan Review Notes
Plan Review Notes For Permit 03100659
Permit Number 03100659
Review Stop P
Sequence Number 1
Notes
Date Text
2003-10-28 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SANITARY RISER DIAGRAM DOES NOT RE-
 FLECT THE FLOOR PLAN, NOR DOES IT MEET
 CODE REQUIREMENTS. THE LAUNDRY ROOM
 HAS A W/M AND A LAUNDRY SINK. NO SINK
 IS SHOWN ON RISER. 104.2.1 - THE WASH
 MACHINE REQUIRES A STANDPIPE. SECTION
 1002.1 & 802.4. - A CLEANOUT IS REQUIRED
 4' ABOVE THE FLOOR AT THE WASH MACHINE
 SECTION 708.10. - THE RISER SHOWS SHOW-
 ERS AND THE FLOOR PLAN SHOWS TUBS. SECT-
 ION 104.2. SEE RED LINE CORRECTIONS TO
 BE MADE TO RISER AND RESUBMIT FOR REVIEW
  