| Notes |
| Date |
Text |
| 2003-10-28 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1) SANITARY RISER DIAGRAM DOES NOT RE- | | | FLECT THE FLOOR PLAN, NOR DOES IT MEET | | | CODE REQUIREMENTS. THE LAUNDRY ROOM | | | HAS A W/M AND A LAUNDRY SINK. NO SINK | | | IS SHOWN ON RISER. 104.2.1 - THE WASH | | | MACHINE REQUIRES A STANDPIPE. SECTION | | | 1002.1 & 802.4. - A CLEANOUT IS REQUIRED | | | 4' ABOVE THE FLOOR AT THE WASH MACHINE | | | SECTION 708.10. - THE RISER SHOWS SHOW- | | | ERS AND THE FLOOR PLAN SHOWS TUBS. SECT- | | | ION 104.2. SEE RED LINE CORRECTIONS TO | | | BE MADE TO RISER AND RESUBMIT FOR REVIEW | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|