| Plan Review Notes For Permit 03100659 |
| Permit Number |
03100659 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-10-27 00:00:00 | ************* UNSAT **************** | | | | | | 1)NOTE: PLEASE SEE ZONING COMMENTS THAT | | | WILL AFFECT ELECTRICAL PLANS. | | | | | | 2)NOTE: PLEASE SEE THAT SEPARATE SERVICE | | | IS NOT PERMITTED. 230.2, 230.72, 230.70 | | | | | | 3)NOTE: PLEASE SEE 210.52C1-5 | | | | | | 4)NOTE: PLEASE PROVIDE ROOM DESIGNATION | | | ON ELECTRICAL PLANS. | | | | | | 5)NOTE: PLEASE CLARIFY IF RISER DIAGRAM | | | SHOWN FOR MAIN HOUSE IS NEW OR EXISTING? | | | | | | 6)NOTE: PLEASE PROVIDE PANEL SCHEDULE(S) | | | WITH AWG/ OCP ETC. | | | PLEASE LIST ALL THE MIN REQ'D CIRCUITS | | | PLEASE LIST THE ARC FAULT PROETCTED | | | CIRCUITS PER 210.12. | | | 2002 NEC | | | | | | PLEASE SEE THAT A FULL REVIEW FOR | | | ELECTRICAL CODE COMPLIANCE CAN NOT BE | | | DONE AT THIS TIME DUE TO MAJOR ELECTRIC- | | | -AL CHANGES. | | | | | | PLEASE SUBMIT FOR REVIEW .IF THERE ARE | | | ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|