| 2003-11-09 00:00:00 | *****CORRECTIONS****** |
| | |
| | SAMANTHA THYNG, BUILDING PLANS EXAMINER |
| | 561-805-6724 |
| | |
| | 1.)PROVIDE A SURVEY FOR THIS JOB. |
| | |
| | 2.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3.)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.THE PLANS MUST BE STAMPED |
| | AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION.233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 4.)THIS IS AN ADDITION OF GREATER |
| | THAN 25% AND MUST COMPLY WITH 3401.7.2. |
| | FBC, 2003 AMENDMENT (GFCI AND SMOKE |
| | DETECTORS IN EXISTING HOUSE). |
| | |
| | 5.)SHEET A1, SITE PLAN, PROVIDE |
| | DIMENSIONS. |
| | |
| | 6.)SHEET C1, SITE PLAN NOTE #14, |
| | REFERS TO SBC103.THE GOVERNING CODE |
| | IS FBC; SECTION 103 REFERS TO POWERS & |
| | DUTIES OF THE BUILDING OFFICIAL. |
| | |
| | 7.)SHEET C1, TRUSS NOTES #9, ROOF |
| | SHEATHING SCHEDULE MUST COMPLY WITH |
| | CITY OF WEST PALM BEACH AMENDMENTS TO |
| | THE FBC, TABLE 2306.1. |
| | |
| | 8.)SHEET C1, WINDOW AND DOOR NOTES, |
| | THE MIN DESIGN PRESSURE IS +-34; |
| | CONFLICTS WITH DESIGN PRESSURES ON |
| | DOOR AND WINDOW SCHEDULES. |
| | |
| | 9.)SHEET A2, WIND DESIGN INFORMATION |
| | INDICATES THAT THE DESIGN OF THE |
| | BUILDING IS BASED ON THE SIMPLIFIED |
| | PROVISIONS OF FBC1606.2.THIS IS FOR |
| | A SIMPLE DIAPHRAGM BUILDING.THE |
| | BREEZEWAY IS NOT ALLOWED PER ZONING; |
| | THE BUILDING NO LONGER QUALIFIES AS A |
| | SIMPLE DIAPHRAGM. |
| | |
| | 10.) FIRESTOP REQUIRED FOR STAIRS, |
| | FBC2305.1.4. |
| | |
| | 11.) WIND DESIGN INFORMATION IS |
| | INCOMPLETE, SEE FBC1606.1.7 2003 |
| | AMENDMENT, SHEET A2. |
| | |
| | 12.) PROVIDE A STRUCTURAL DETAIL FOR |
| | THE STAIRS. |
| | |
| | 13.) PROVIDE A GUARDRAIL DETAIL, COMPLY |
| | WITH FBC1015, 1608. |
| | |
| | 14.) STAIR RAIL TO COMPLY WITH FBC1608. |
| | |
| | 15.) DESIGN GRAVITY LOADS, A3 & A7(UNDER |
| | THE WALL SCHEDULE), REQUIRES A BOTTOM |
| | CHORD LIVE LOAD OF 10 FOR ATTICS WITHOUT |
| | STORAGE, 30 FOR ATTICS WITH STORAGE, |
| | FBC TABLE 1604.1. |
| | |
| | 16.) WINDOW G, 2ND FLOOR OF DETACHED |
| | BUILDING, A3, TO COMPLY WITH FBC2405.1 |
| | (SAFETY GLASS). |
| | |
| | 17.) PROVIDE A SOILS INVESTIGATION |
| | REPORT. |
| | |
| | 18.) SHEETS A4, A5, A6, WALL SECTION |
| | REQUIRES THE FINISHED FLOOR TO BE MIN |
| | 4" ABOVE FINISHED GRADE, CITY OF WEST |
| | PALM BEACH AMEND. TO THE FBC1804.1.7. |
| | 12" MIN BELOW GRADE REQUIRED FOR THE |
| | FOOTER, FBC1804.1.3. |
| | |
| | 19.)SHEET A10, HEAD AND SILL DETAILS |
| | FOR WINDOWS, NOTE THAT HURRICANE |
| | SHUTTERS MUST BE INSTALLED HORIZONTALLY |
| | FOR THOSE OPENINGS BASED ON THIS DETAIL. |
| | |
| | 20.)PROVIDE A HURRICANE SHUTTER |
| | INSTALLATION SCHEDULE, SEE ATTACHED, |
| | PER CITY OF WEST PALM BEACH POLICY. |
| | |
| | 21.) STATEWIDE OR LOCAL PRODUCT |
| | APPROVAL IS REQUIRED FOR ALL PRODUCTS, |
| | INCLUDING STRUCTURAL, FAC 9B-72.050, |
| | EFFECTIVE OCTOBER 1, 2003.FOR MORE |
| | INFORMATION, SEE THE DCA WEBSITE AT |
| | WWW.DCA.STATE.FL.US/FHCD/FBC/COMMITTEES/ |
| | PRODUCT_APPROVAL/1_PRODUCT_APPROVAL.HTM |
| | |
| | 22.) THE PRODUCT APPROVAL FOR THE PGT |
| | SINGLE HUNG WINDOW IS ILLEGIBLE.THE |
| | CASEMENT PRODUCT APPROVAL IS FOR A |
| | DOUBLE (OPERABLE MULLED TO FIXED),SINGLE |
| | WINDOW IS NOT COVERED BY THIS PRODUCT |
| | APPROVAL.THE 6'X6' PICTURE WINDOW |
| | EXCEEDS THE MAXIMUM RECTANGULAR WINDOW |
| | SIZE COVERED BY THE PRODUCT APPROVAL |
| | SUBMITTED (OK FOR ARCHED WINDOW). |
| | |
| | 23.)THE FOLLOWING PRODUCT APPROVALS |
| | ARE NEEDED: |
| | STATEWIDE PRODUCT APPROVAL FOR ALL |
| | DADE COUNTY NOAS SUBMITTED AND |
| | CONDITIONALLY APPROVED (SPANISH S, |
| | 16X8 GAR DOOR, STORM PANELS, PGT |
| | OUTSWING FR DOOR,STANLEY OUTSWING |
| | GLAZED DOOR, ALUM FG WINDOW) |
| | INSWING FRENCH DOOR |
| | SINGLE HUNG WINDOW |
| | MULLION |
| | OUTSWING METAL DOOR |
| | 6'X6' FIXED GLASS WINDOW |
| | CASEMENT WINDOW |
| | |
| | 24.)PROVIDE A DRAFTSTOP DETAIL AND |
| | SCHEDULE, BOTH BUILDINGS, FBC705.3. |
| | |
| | 25.)WALL SECTION, SHEETS A4, A5, A6, |
| | FIRESTOP REQUIRED FBC705.3. |
| | |
| | 26.) WALL SCHEDULES, A3, A7, A8, |
| | SPECIFIES R30 INSULATION FOR A 4"OR6" |
| | WALL.IS THIS CORRECT?CONFLICTS WITH |
| | WALL SECTION. |
| | |
| | 27.) WALL SECTION, A6, STUCCO IS |
| | REQUIRED TO BE 7/8" HORIZONTAL |
| | APPLICATION OVER WIRE LATH, FBC2504.2.2, |
| | ASTM C926. |
| | |
| | 28.) ADDITIONAL FEES DUE (VALUE |
| | ADJUSTMENT, RADON), $125.18, SEE |
| | ATTACHED BZ233272. |