2004-08-12 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)STUCCO IN A VERTICAL APPLICATION
 OVER WIRE LATH IS TO BE 3 COAT, 7/8"
 MINIMUM, FBC2504.2.2, ASTM C926.
 REVISE AM A1.04, DETAIL W8, AND ANY
 OTHER DETAILS AFFECTED.
  
 2.)THE PRINTED NAME OF THE PERSON
 SEALING THE DOCUMENT IS TO BE ON THE
 SHEET.ALSO, SOME SHEETS WERE NOT
 SEALED.
  
 3.)IN REGARDS TO FORMAT FOR
 RESUBMITTAL, PLEASE CALL TO DISCUSS
 (NUMBER OF COPIES, UNDER WHICH PERMIT
 NUMBER) BEFORE RESUBMITTAL.