| 2004-12-31 00:00:00 | PROVISO: |
| | 1.PLAN SHEET AP/M15.03 DETAIL OF THE |
| | WALL HUNG UNIT.PER 2001 FBC(M)603.1.3, |
| | 4" MINIMUM IS REQUIRED AROUND THE AHU. |
| | |
| | 2.PLAN SHEET AP/M15.01, PLAN DOES NOT |
| | INDICATE RADIATION DAMPERS THAT ARE |
| | REQUIRED DUE TO THE BUILDING TYPE.SEE |
| | PLAN SHEET AP/15.03 FOR INSTALLATION |
| | DETAIL FOR THE REQUIRED DAMPERS.THIS |
| | IS REQUIRED AT EACH GRILLE. |
| | |
| | 3.PLAN SHEET CH/M15.01 IS NOT |
| | APPROVED.FIRE DAMPERS ARE REQUIRED AT |
| | THE DUCT PENETRATIONS THROUGH THE WALL |
| | AT THE LAUNDRY ROOM.REFERENCE PLAN |
| | SHEET AM/A1.04(REVISED 10/4/04), DETAIL |
| | FOR THE WALL ASSEMBLY FOR THE "INTERIOR |
| | RATED WALL @ CLUBHOUSE LAUNDRY" (W-3), |
| | THIS REQUIRES FIRE DAMPERS FOR THE |
| | PENTRATIONS. |
| | |
| | EXCEPTION TO FIRE DAMPERS ARE AS |
| | FOLLOWS: |
| | 1.DUCT SHALL NOT EXCEED 100 SQ |
| | INCHES. |
| | 2.THE DUCT SHALL BE OF .0217" MINIMUM |
| | STEEL. |
| | 3.DUCT SHALL CONTINUE A MINIMUM OF 5 |
| | FT FROM RATED WALL ON HAVE NO OPENINGS |
| | WITHIN 5 FT OF THE PENETRATION. |
| | 4.DUCT SHALL BE INSTALLED ABOVE THE |
| | CEILING. |
| | |