2004-12-31 00:00:00PROVISO:
 1.PLAN SHEET AP/M15.03 DETAIL OF THE
 WALL HUNG UNIT.PER 2001 FBC(M)603.1.3,
 4" MINIMUM IS REQUIRED AROUND THE AHU.
  
 2.PLAN SHEET AP/M15.01, PLAN DOES NOT
 INDICATE RADIATION DAMPERS THAT ARE
 REQUIRED DUE TO THE BUILDING TYPE.SEE
 PLAN SHEET AP/15.03 FOR INSTALLATION
 DETAIL FOR THE REQUIRED DAMPERS.THIS
 IS REQUIRED AT EACH GRILLE.
  
 3.PLAN SHEET CH/M15.01 IS NOT
 APPROVED.FIRE DAMPERS ARE REQUIRED AT
 THE DUCT PENETRATIONS THROUGH THE WALL
 AT THE LAUNDRY ROOM.REFERENCE PLAN
 SHEET AM/A1.04(REVISED 10/4/04), DETAIL
 FOR THE WALL ASSEMBLY FOR THE "INTERIOR
 RATED WALL @ CLUBHOUSE LAUNDRY" (W-3),
 THIS REQUIRES FIRE DAMPERS FOR THE
 PENTRATIONS.
  
 EXCEPTION TO FIRE DAMPERS ARE AS
 FOLLOWS:
 1.DUCT SHALL NOT EXCEED 100 SQ
 INCHES.
 2.THE DUCT SHALL BE OF .0217" MINIMUM
 STEEL.
 3.DUCT SHALL CONTINUE A MINIMUM OF 5
 FT FROM RATED WALL ON HAVE NO OPENINGS
 WITHIN 5 FT OF THE PENETRATION.
 4.DUCT SHALL BE INSTALLED ABOVE THE
 CEILING.
  