| Plan Review Notes For Permit 03100653 |
| Permit Number |
03100653 |
|
| Review Stop |
B |
| Sequence Number |
47 |
|
| Notes |
| Date |
Text |
| 2005-06-03 00:00:00 | ****CORRECTIONS**** | | | STAIR SHOPS | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)THE HANDRAIL EXTENSION AT THE TOP | | | OF THE STAIRS IS TO COMPLY WITH FBC11 | | | FIGURE 19, FBC11-4.94(6). | | | | | | 2.)DELEGATED ENGINEERING AND | | | SUBMITTALS TO BE REVIEWED BY ARCHITECT | | | OR ENGINEER OF RECORD. | | | | | | 3.)THE GUARDRAIL IS TO COMPLY WITH | | | FBC1015.2. | | | | | | 4.)A TITLE BLOCK IS REQUIRED FOR THE | | | ENGINEER WHO SEALED THE PLAN, | | | FAC61G15-23.002.A SEAL ON EACH SHEET | | | IS REQUIRED, NOT ONLY THE COVER SHEET. | | | | | | 5.)WHAT IS UNDER THE STAIRS? | | | FBC1006.1.4. | | | | | | 6.)PLEASE RESUBMIT PREVIOUSLY DENIED | | | RAILING SHOPS AND CALCS. |
|