| 2005-03-17 00:00:00 | ****CORRECTIONS**** |
| | STAIR SHOPS AND HANDRAIL CALCS |
| | PREPARED BY DR COWAN, PE 2/16/05 |
| | |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)DETAIL B-E1 SHOWS "VARIES" FOR |
| | RISER HEIGHTS.RISERS ARE TO BE IN |
| | COMPLIANCE WITH FBC1007.3 AND ARE |
| | LIMITED IN THE AMOUNT OF VARIATION BY |
| | FBC1007.3.3. |
| | |
| | 2.)FBC1007.5.5, THE HANDRAIL IS TO |
| | EXTEND AT LEAST 12" AT THE TOP OF THE |
| | FLIGHT; NOTE DIMENSION ON A-E1. |
| | |
| | 3.)THE CALCULATIONS REFER TO THE WRONG |
| | BUILDING CODE (IBC).PLANS ARE TO BE |
| | COMPLIANT WITH THE GOVERNING CODE, |
| | FBC2001. |
| | |
| | 4.)PLEASE SEE FBC1608.2.HANDRAILS |
| | ARE TO COMPLY WITH FBC1608.2.1 (NO |
| | HANDRAIL CALCS PROVIDED) AND GUARDRAILS |
| | ARE TO COMPLY WITH FBC1608.2.2 (HANDRAIL |
| | DESIGN CRITERIA CALCS PROVIDED FOR |
| | GUARDRAILS). |
| | |
| | 5.)A TITLE BLOCK IS REQUIRED FOR ALL |
| | SHEETS IN COMPLIANCE WITH |
| | FAC61G15-23.002.SOME INFORMATION |
| | MISSING; CERTIFICATE OF AUTHORIZATION |
| | NUMBER FOR DR COWAN & ASSOC, PRINTED |
| | LICENSE NUMBER FOR THE PERSON SEALING |
| | THE DOCUMENT, TITLE BLOCK ON SHEETS E1 |
| | AND E2.PLEASE READ THE FAC FOR |
| | REQUIREMENTS AND INCLUDE ALL INFORMATION |
| | REQUIRED. |