Plan Review Notes
Plan Review Notes For Permit 03100653
Permit Number 03100653
Review Stop P
Sequence Number 4
Notes
Date Text
2004-05-14 00:00:00PASSED/PROVISO
 REVISION REQUIRED FOR SHEET CH/P14.02
  
 1) SHT CH/P14.02 WATER HAMMER ARRESTORS
 SHALL BE LOCATED NEAR THE FIXTURES IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING AS
 SHOWN. PDI-WH 201 AND MANUF. INSTALLAT-
 ION INSTRUCTIONS. WATER HAMMER ARRESTOR
 REQUIRED AT EACH WASH MACHINE.
  
 2) INDICATE ON PLANS THAT AN RPZ BACK-
 FLOW IS REQUIRED ON THE WATER SERVICE TO
 THE CLUBHOUSE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]