Plan Review Notes
Plan Review Notes For Permit 03100653
Permit Number 03100653
Review Stop E
Sequence Number 4
Notes
Date Text
2004-05-08 00:00:00*********** UNSAT *******************
  
 1)NOTE: NO EQUIPMENT GROUNDING CONDUCTOR
 FROM METER TO MAIN/ FIRST MEANS OF
 DISCONNECT. 250.6,250.24
  
 2)NOTE: PLEASE SHOW/INDICATE ALL RECCEPT
 -S SHOWN IN GARAGE AS GFI/GFI PROTECTED
 210.8
  
 3 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
 PLEASE SEE ALL SHEETS, ADJUST ALL LOADS
 CALCS.
  
 4)NOTE: PLANS INDICATE NOTE FOR EM LTS
 TO BE WIRED AHEAD OF LOCAL CIRCUITS,
 PLEASE SHOW CIRCUIT #'S.
  
 5)NOTE: PLEASE SEE LOADS SHOWN FOR HP
 E16.02 PLEASE SHOW ALL CONTINUOUS LOAD
 -S AT 125%(LIGHTING ETC)(LARGEST MOTORS)
 215.2,215.3,230.42,210.19A,210.20A ETC
  
 6)NOTE: PLEASE SEE E16-.02, NOTE MENTION
 -S NO ALUM FOR GROUNDING OR BONDING,
 YET FEEDER SCHEDULE STILLS NOTES AND
 DEATILS ALUM AS EQUIPMENT GRNDS.
  
 7)NOTE: PLEASE SEE AP E16.00.
 PLEASE INDICATE RATING OF POLES AND LTS
 TO BE RATED FOR FBC 140 MPH.
  
 PLANS HAVE NOW BEEN CHANGED TO BE A
 MASTER. ALL CORRECTIONS MUST BE DONE,
 NO REDLINES CAN BE DONE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  