| 2004-04-14 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 |
| | |
| | 1.)AS DISCUSSED WITH OWNER'S |
| | REPRESENTATIVE, THE ARCHITECTURAL SITE |
| | PLAN WILL BE REMOVED FROM THE PLAN AND |
| | SUBSTITUTED WITH THE SITE PLAN PREPARED |
| | BY JON E. SCHMIDT AND ASSOCIATES.WE |
| | WILL FOLLOW THE NAMING CONVENTION ON |
| | THAT SITE PLAN (BUILDINGS A-I, WITH |
| | THE CLUBHOUSE AS BUILDING A) AND |
| | DISREGARD THE NAMING CONVENTION ON THE |
| | CIVILS AND ARCHITECTURALS AS PER OWNER'S |
| | REPRESENTATIVE.**SUBJECT TO ZONING** |
| | HAVE THE SITE PLAN REVIEWED AND APPROVED |
| | BY THE DESIGNER OF RECORD.HAVE A NOTE |
| | PROVIDED ON THE SITE PLAN REFERRING TO |
| | THE CIVIL PAVING PLAN FOR SIDEWALK |
| | ELEVATIONS. |
| | |
| | 2.)PROVIDE A COPY OF THE DEED SHOWING |
| | OWNERSHIP. |
| | |
| | 3.) A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 4.)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.THE PLANS MUST BE STAMPED |
| | AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION. |
| | |
| | 5.)THE ENERGY CALCS SUBMITTED ARE NOT |
| | CORRECT.THERE SHOULD BE A DIFFERENT |
| | EN CALCS FOR THE 1ST, 2ND AND 3RD FLOOR |
| | UNITS AS THE INSULATION IS DIFFERENT FOR |
| | EACH.THERE SHOULD BE FLOOR INSULATION |
| | INDICATED FOR 2ND AND 3RD FLOOR, NOT NA. |
| | THERE SHOULD BE UNDER ATTIC INSULATION |
| | FOR THE 3RD AND 2ND FLOOR UNITS AS |
| | APPLICABLE, BUT 1ST FLOOR HAVE A SINGLE |
| | ASSEMBLY.SUBMIT CORRECTED ENERGY |
| | CALCS.PLEASE PROVIDE A PRINTED NAME, |
| | ADDRESS, LICENSE NUMBER FOR THE PERSON |
| | PREPARING THE ENERGY CALC ON THAT SHEET. |
| | REFER TO THE PERMIT NUMBERS AND PROVIDE |
| | ONE EXTRA COPY OF THE FIRST SHEET OF |
| | EACH ENERGY CALC FOR SUBMITTAL TO THE |
| | STATE, FBC13. |
| | |
| | 6.)LINE 9B, UNIT C1, INDICATES 0 |
| | INSULATION, NONCOMPLIANT WITH FBC13 |
| | CHAPTER 6 (METHOD 600A, ENERGY CALC). |
| | |
| | 7.)THE FORM 400A INDICATES A NET AREA |
| | OF 2979; THE PLAN (CH A5.01) INDICATES |
| | AN A/C AREA OF 3546 (METHOD 400A |
| | ENERGY CALC). |
| | |
| | 8.)THE MEDIAN ROOF HEIGHT IS GIVEN AS |
| | 35', AP S4.01.TABLES 1606.2B AND |
| | TABLE 1606.2C ARE LIMITED TO BUILDINGS |
| | WITH A MEAN ROOF HEIGHT OF LESS THAN |
| | 30'. ADDRESS.THE PRODUCT APPROVALS FOR |
| | THE WINDOWS AND DOORS CANNOT BE |
| | REVIEWED UNTIL DESIGN PRESSURES ARE |
| | PROVIDED. (APARTMENT BUILDINGS) |
| | |
| | 9.)DESIGN PRESSURES FOR THE APARTMENT |
| | AND CLUBHOUSE ROOFS HAVE NOT |
| | BEEN PROVIDED.TABLE 1606.2C INDICATES |
| | PRESSURES IN THE -50S; NOA 02-0328.05 |
| | SUBMITTED (ROOF TILE, CLUBHOUSE) HAS |
| | A LIMITATION OF 45.8.PROVIDE A ROOF |
| | DESIGN PRESSURE FOR BOTH BUILDINGS. |
| | PROVIDE COMPLIANT PRODUCT APPROVALS OR |
| | SEPARATE PERMITS FOR THE ROOFS WILL |
| | BE REQUIRED. |
| | |
| | 10.)DETAIL 7, SHEET CH S4.01 LACKS A |
| | ZONE 3 FOR THE HIP ROOF, SEE FBC FIG. |
| | 1606.2. (SEE PREVIOUS LIST, ITEM 18). |
| | |
| | 11.) THE PRODUCT APPROVAL FOR THE ROOF |
| | SHINGLES SUBMITTED (NOA02-1216.05) HAS |
| | A LIMITATION (4.2), "SHALL NOT BE |
| | INSTALLED ON ROOF MEAN HEIGHTS IN |
| | EXCESS OF 33 FT."THIS PRODUCT APPROVAL |
| | IS ACCEPTABLE FOR THE MAIL KIOSK BUT |
| | NOT THE APARTMENT BUILDINGS.ADDRESS. |
| | |
| | 12.) A PROVISO HAS BEEN ADDED TO YOUR |
| | PRODUCT APPROVALS THAT ALL WINDOWS |
| | ARE TO BE IMPACT GLASS AS PER YOUR |
| | ARCHITECT'S LETTER. |
| | |
| | 13.) THE PRODUCT APPROVALS SUBMITTED |
| | PREVIOUSLY NEED FLORIDA STATEWIDE, LOCAL |
| | OR SITE SPECIFIC PRODUCT APPROVALS |
| | FAC9B-72. |
| | |
| | 14.) SUBMIT THE FOLLOWING PRODUCT |
| | APPROVALS: |
| | GARAGE DOOR (MAINT BLDG) |
| | LOUVERED DOOR (MAIL KIOSK) |
| | |
| | 15.)SEPARATE PERMITS REQUIRED FOR THE |
| | POOL, FENCES AND SIGN. |
| | |
| | 16.)PRODUCT APPROVALS NOT SUBMITTED |
| | PROPERLY FOR REVIEW BEFORE PERMIT |
| | ISSUANCE WILL REQUIRE SEPARATE PERMITS. |