2004-04-14 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
  
 1.)AS DISCUSSED WITH OWNER'S
 REPRESENTATIVE, THE ARCHITECTURAL SITE
 PLAN WILL BE REMOVED FROM THE PLAN AND
 SUBSTITUTED WITH THE SITE PLAN PREPARED
 BY JON E. SCHMIDT AND ASSOCIATES.WE
 WILL FOLLOW THE NAMING CONVENTION ON
 THAT SITE PLAN (BUILDINGS A-I, WITH
 THE CLUBHOUSE AS BUILDING A) AND
 DISREGARD THE NAMING CONVENTION ON THE
 CIVILS AND ARCHITECTURALS AS PER OWNER'S
 REPRESENTATIVE.**SUBJECT TO ZONING**
 HAVE THE SITE PLAN REVIEWED AND APPROVED
 BY THE DESIGNER OF RECORD.HAVE A NOTE
 PROVIDED ON THE SITE PLAN REFERRING TO
 THE CIVIL PAVING PLAN FOR SIDEWALK
 ELEVATIONS.
  
 2.)PROVIDE A COPY OF THE DEED SHOWING
 OWNERSHIP.
  
 3.) A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 4.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.
  
 5.)THE ENERGY CALCS SUBMITTED ARE NOT
 CORRECT.THERE SHOULD BE A DIFFERENT
 EN CALCS FOR THE 1ST, 2ND AND 3RD FLOOR
 UNITS AS THE INSULATION IS DIFFERENT FOR
 EACH.THERE SHOULD BE FLOOR INSULATION
 INDICATED FOR 2ND AND 3RD FLOOR, NOT NA.
 THERE SHOULD BE UNDER ATTIC INSULATION
 FOR THE 3RD AND 2ND FLOOR UNITS AS
 APPLICABLE, BUT 1ST FLOOR HAVE A SINGLE
 ASSEMBLY.SUBMIT CORRECTED ENERGY
 CALCS.PLEASE PROVIDE A PRINTED NAME,
 ADDRESS, LICENSE NUMBER FOR THE PERSON
 PREPARING THE ENERGY CALC ON THAT SHEET.
 REFER TO THE PERMIT NUMBERS AND PROVIDE
 ONE EXTRA COPY OF THE FIRST SHEET OF
 EACH ENERGY CALC FOR SUBMITTAL TO THE
 STATE, FBC13.
  
 6.)LINE 9B, UNIT C1, INDICATES 0
 INSULATION, NONCOMPLIANT WITH FBC13
 CHAPTER 6 (METHOD 600A, ENERGY CALC).
  
 7.)THE FORM 400A INDICATES A NET AREA
 OF 2979; THE PLAN (CH A5.01) INDICATES
 AN A/C AREA OF 3546 (METHOD 400A
 ENERGY CALC).
  
 8.)THE MEDIAN ROOF HEIGHT IS GIVEN AS
 35', AP S4.01.TABLES 1606.2B AND
 TABLE 1606.2C ARE LIMITED TO BUILDINGS
 WITH A MEAN ROOF HEIGHT OF LESS THAN
 30'. ADDRESS.THE PRODUCT APPROVALS FOR
 THE WINDOWS AND DOORS CANNOT BE
 REVIEWED UNTIL DESIGN PRESSURES ARE
 PROVIDED. (APARTMENT BUILDINGS)
  
 9.)DESIGN PRESSURES FOR THE APARTMENT
 AND CLUBHOUSE ROOFS HAVE NOT
 BEEN PROVIDED.TABLE 1606.2C INDICATES
 PRESSURES IN THE -50S; NOA 02-0328.05
 SUBMITTED (ROOF TILE, CLUBHOUSE) HAS
 A LIMITATION OF 45.8.PROVIDE A ROOF
 DESIGN PRESSURE FOR BOTH BUILDINGS.
 PROVIDE COMPLIANT PRODUCT APPROVALS OR
 SEPARATE PERMITS FOR THE ROOFS WILL
 BE REQUIRED.
  
 10.)DETAIL 7, SHEET CH S4.01 LACKS A
 ZONE 3 FOR THE HIP ROOF, SEE FBC FIG.
 1606.2. (SEE PREVIOUS LIST, ITEM 18).
  
 11.) THE PRODUCT APPROVAL FOR THE ROOF
 SHINGLES SUBMITTED (NOA02-1216.05) HAS
 A LIMITATION (4.2), "SHALL NOT BE
 INSTALLED ON ROOF MEAN HEIGHTS IN
 EXCESS OF 33 FT."THIS PRODUCT APPROVAL
 IS ACCEPTABLE FOR THE MAIL KIOSK BUT
 NOT THE APARTMENT BUILDINGS.ADDRESS.
  
 12.) A PROVISO HAS BEEN ADDED TO YOUR
 PRODUCT APPROVALS THAT ALL WINDOWS
 ARE TO BE IMPACT GLASS AS PER YOUR
 ARCHITECT'S LETTER.
  
 13.) THE PRODUCT APPROVALS SUBMITTED
 PREVIOUSLY NEED FLORIDA STATEWIDE, LOCAL
 OR SITE SPECIFIC PRODUCT APPROVALS
 FAC9B-72.
  
 14.) SUBMIT THE FOLLOWING PRODUCT
 APPROVALS:
 GARAGE DOOR (MAINT BLDG)
 LOUVERED DOOR (MAIL KIOSK)
  
 15.)SEPARATE PERMITS REQUIRED FOR THE
 POOL, FENCES AND SIGN.
  
 16.)PRODUCT APPROVALS NOT SUBMITTED
 PROPERLY FOR REVIEW BEFORE PERMIT
 ISSUANCE WILL REQUIRE SEPARATE PERMITS.