| Plan Review Notes For Permit 03100653 |
| Permit Number |
03100653 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-03-09 00:00:00 | DENIED: | | | 1.REFERENCE RESPONSE LETTER DATED | | | 2-19-04; RESPONSE #1 - "REVISE AP/M15.01 | | | TO INCLUDE OUTSIDE AIR DUCTS TO AHU'S. | | | PLEASE INDICATE ON THE PLAN AN OUTSIDE | | | AIR SCHEDULE SHOWING COMPLIANCE WITH | | | TABLE 403.3. | | | | | | 2.RESPONSE #2 - "REFER TO DETAIL ON | | | AP/A15.01". DETAIL INDICATES A RATED | | | WALL AND NOT A VENTED SHAFT AS REQUIRED | | | IN ASHRAE 15-92 SECTIOIN 11.12.3 (A) | | | THROUGH (C). | | | | | | 3.AUXILIARY DRAIN PAN WITH OVERFLOW | | | PROTECTION REQUIRED PER 2001 FBC(M) | | | 307.2.3. | | | | | | PER CONVERSATION WITH GIL (ENGINEER), | | | WAITING STATE RULING ON WHICH ASHRAE | | | STANDARD WE ARE UNDER.CHAPTER 15 | | | INDICATES 15-94 & NOT 15-2001. | | | | | | COMMENT #3 WILL BE ADDRESSED/PLAN WILL | | | INDICATE A 4" CLEARANCE AROUND THE AHU. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|