Plan Review Notes
Plan Review Notes For Permit 03100653
Permit Number 03100653
Review Stop M
Sequence Number 3
Notes
Date Text
2004-03-09 00:00:00DENIED:
 1.REFERENCE RESPONSE LETTER DATED
 2-19-04; RESPONSE #1 - "REVISE AP/M15.01
 TO INCLUDE OUTSIDE AIR DUCTS TO AHU'S.
 PLEASE INDICATE ON THE PLAN AN OUTSIDE
 AIR SCHEDULE SHOWING COMPLIANCE WITH
 TABLE 403.3.
  
 2.RESPONSE #2 - "REFER TO DETAIL ON
 AP/A15.01". DETAIL INDICATES A RATED
 WALL AND NOT A VENTED SHAFT AS REQUIRED
 IN ASHRAE 15-92 SECTIOIN 11.12.3 (A)
 THROUGH (C).
  
 3.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 PER CONVERSATION WITH GIL (ENGINEER),
 WAITING STATE RULING ON WHICH ASHRAE
 STANDARD WE ARE UNDER.CHAPTER 15
 INDICATES 15-94 & NOT 15-2001.
  
 COMMENT #3 WILL BE ADDRESSED/PLAN WILL
 INDICATE A 4" CLEARANCE AROUND THE AHU.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.