| 2004-03-12 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 |
| | |
| | 1.)DUE TO THE SCOPE AND NATURE OF THE |
| | PROPOSED WORK THE BUILDING OFFICIAL WILL |
| | REQUIRE A RESIDENT INSPECTOR AS PROVIDED |
| | FOR IN FBC 105.3 AS AMENDED BY THE CITY |
| | OF WEST PALM BEACH.CONTACT HAROLD |
| | PISKURA FOR MORE INFORMATION, |
| | 561-805-6711.THIS MUST BE DONE BEFORE |
| | A PERMIT CAN BE ISSUED. |
| | |
| | 2.)NOTE 10, LUMBER AND FRAMING, SHEET |
| | AP/A1.03 HAS BEEN REVISED TO STATE |
| | "NON BEARING", BUT PER OUR CONVERSATION |
| | MUST BE ALSO FOR INTERIOR WALLS ONLY. |
| | |
| | 3.)SEE PREVIOUS LISTS IN REGARDS TO |
| | THE REQUEST FOR TOPOGRAPHICAL |
| | AND DIMENSIONAL INFORMATION PERTINENT |
| | TO BUILDING LOCATION AND ACCESSIBILITY. |
| | THE TRANSMITTAL LETTER INDICATES THAT |
| | THE CIVIL DRAWINGS HAVE BEEN REVISED. |
| | AS CIVIL DRAWINGS ARE NOT A PART OF THIS |
| | PACKAGE, PLEASE REVISE THE |
| | ARCHITECTURALS TO PROVIDE THIS |
| | INFORMATION AS REQUIRED BY FBC TABLE |
| | 600 AND CHAPTER 11. |
| | |
| | 4.)BEFORE A PERMIT TO CONSTRUCT CAN |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY.THE PLANS MUST BE |
| | STAMPED AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION.233-5025 |
| | |
| | 5.)DUMPSTER REQUIRES A SEPARATE |
| | PERMIT. |
| | |
| | 6.)THE FOLLOWING PRODUCT APPROVALS |
| | WERE NOT SUBMITTED: |
| | ROOF |
| | SHUTTERS, IF APPLICABLE |
| | SINGLE HUNG WINDOWS |
| | MULLIONS |
| | |
| | FLORIDA STATEWIDE, LOCAL OR SITE |
| | SPECIFIC PRODUCT APPROVAL REQUIRED. |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | 7.)SEE PREVIOUS LIST, PROVIDE A COPY |
| | OF THE RECORDED PLAT FOR ADDRESSING |
| | PURPOSES. |
| | |
| | 8.)ADDITIONAL FEES DUE. |
| | |
| | 9.)SEE PREVIOUS LIST, ITEM #11, |
| | THERE ARE STILL REFERENCES ON THE |
| | PLAN TO THE EXPIRED MAGNA WALL 1997 (FOR |
| | INSTANCE, W-10 AP A1.04, W-1 AM A1.04). |
| | |
| | 10.) SEE PREVIOUS LIST, ITEM #12. |
| | IMPACT PROTECTION REQUIRED.2ND AND 3RD |
| | FLOOR REQUIRES IMPACT GLASS.SEE |
| | ATTACHED POLICY IN REGARDS TO MISSILE |
| | IMPACT PROTECTION, ITEM #13.THE |
| | INSTALLATION PLAN FOR HURRICANE |
| | PROTECTION IS REQUIRED TO BE APPROVED |
| | BEFORE PERMIT ISSUANCE. |
| | |
| | 11.)SEE PREVIOUS LIST, PROVIDE |
| | FIRE RATING INFORMATION FOR DOOR TYPE |
| | D, AP9.01. |
| | |
| | 15.)SEE PREVIOUS LIST, FASTENING FOR |
| | SIMPSON CS16 (AP S4.01) CONFLICTS WITH |
| | THE CATALOG.ADDRESS - EITHER CHANGE |
| | TO BE CONSISTENT WITH THE MFGR SPEC OR |
| | SUBMIT CALCULATIONS.CHECK ALL |
| | CONNECTORS. |
| | |
| | 16.)SEE PREVIOUS LIST, PROVIDE A |
| | SOILS INVESTIGATION REPORT, FBC104.3.1.1 |
| | (8). |
| | |
| | 17.)PROVIDE A SURVEY FOR THIS |
| | PROPERTY. |
| | |
| | 18.)S4.01, THE HIP ROOF DOES NOT |
| | INDICATE A ZONE 3. |
| | |
| | 19.)SIGN THE OWNER/AGENT LINE OF THE |
| | ENERGY CALC. |
| | |
| | 20.)THE PRINTED NAME AND LICENSE # |
| | OF THE PERSON SEALING THE PLAN IS |
| | REQUIRED TO BE ON EACH SHEET, FAC |
| | 61G1-16.003, 004. |