Plan Review Notes
Plan Review Notes For Permit 03100653
Permit Number 03100653
Review Stop P
Sequence Number 2
Notes
Date Text
2003-12-24 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
  
 1) SPECIFICATION "A" OR"B" SHALL BE IN-
 DICATED ON PLANS PER REQUIREMENT 7B OF
 THE FHA DESIGN MANUAL. - RESPONSE NOTED,
 BUT NOT REVISED SHEET AP/A5.04 FOUND.
 2) SHTS AP/P14.02 & AP/P14.04 CLEANOUTS
 SHALL BE LOCATED IN THE BREEZEWAYS IN
 ORDER TO COMPLY WITH SECTION 708.3.2
 LOCATED NOT MORE THAN 100' APART. 2 WAY
 CLEANOUT WILL WORK.
 3) SHT AP/P1404 THE DISCHARGE PIPE SHALL
 NOT HAVE ANY TRAPPED SECTIONS AND SHALL
 HAVE A VISIBLE AIR GAP OR AIR GAP FITT-
 ING LOCATED IN THE SAME ROOM AS THE
 WATER HEATER. RESPONSE STATES T & P TO
 DISCHARGE INTO DRAIN PAN BUT RELIEF
 VALVE PIPING DIAGRAM STILL SHOWS T&P
 PIPED UNDER SLAB. PLEASE CLAIRFY. SEC.
 504.7.1
 4) AN RPZ BACKFLOW IS REQUIRED FOR EACH
 BUILDING. RESPONSE NOTED, BUT SHOW ON
 PLANS AS TYPICAL FOR EACH BLDG ON THE
 INLET OF BLDG. FOR REFERENCE.
 5) SHT AP/P14.01 WATER RISER DIAGRAMS,
 THE WATER HAMMER ARRESTORS ARE STILL
 SHOWN IN CEILING. SHOW WATER HAMMER
 ARRESTORS NEAR THE FIXTURES AS REQUIRED
 BY PDI-WH 201 AND MANUF. INSTALL. INSTR.
 6) SEE ATTACHED SHEET CONCERNING FS
 533.80(2)(B) DESIGN PROFESSIONAL DOC-
 UMENTS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]