Plan Review Notes
Plan Review Notes For Permit 03100653
Permit Number 03100653
Review Stop M
Sequence Number 2
Notes
Date Text
2003-12-31 00:00:00DENIED:
 APARTMENTS
 1.PER 2001 FBC(M) 403.3, OCCUPANCY
 TYPE R-2 (MULTI-FAMILY) REQUIRES
 OUTSIDE AIR.ONLY ONE & TWO FAMILY
 DWELLINGS (R-3) ARE EXEMPT FROM 403.3.
 PLEASE REVISE AND SHOW COMPLIANCE WITH
 TABLE 403.3.
  
 2.PLEASE NOTE, REFRIGERANT LINES
 INSTALLED VERTICALLY THROUGH FLOORS
 SHALL COMPLY WITH ASHRAE 15-92 SECTION
 11.12.3 (A) THROUGH (C).
  
 CLUBHOUSE:
 NO COMMENTS
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.