| Plan Review Notes For Permit 03100653 |
| Permit Number |
03100653 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-01-15 00:00:00 | PLAN WAS ORIGINALLY REVIEWED ON | | | 12.24.03. | | | | | | 1) SITE PLAN DOES NOT SHOW REQUIRED | | | FIRE HYDRANTS. | | | | | | 2) FIRE EXTINGUISHERS IN CABINETS SHALL | | | BE A MINIMUM OF 5 LBS. NOT 4 LBS. | | | AS SHOWN ON THE PLANS. | | | | | | 3) TACTILE SIGNAGE REQUIRED AT | | | STAIRWAYS. | | | | | | 4) BUILDING ADDRESS IS REQUIRED ON | | | CLUBHOUSE. | | | | | | 5) AUDIBLE AND VISUAL FIRE ALARM | | | DEVICES ARE REQUIRED IN HANDICAP | | | APARTMENTS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|