| 2004-01-05 00:00:00 | ************** UNSAT ********** |
| | |
| | PLEASE SEE THAT SOME NOTES FROM FIRST |
| | REVIEW STILL NEED TO BE ADDRESSED. |
| | |
| | 1)NOTE: PLEASE SEE THAT IT APPEARS |
| | SOME OF THE CORRECTIONS WERE MADE TO |
| | SOME SHEETS AND THOSE SHEETS WERE |
| | INSERTED, HOWEVER A NEW AP16.02 WAS NOT |
| | SUBMITTED. PLEASESEE THE FOLLOWING |
| | COMMENTS. |
| | |
| | 2)NOTE: PLEASE SEE RESPONSE #1 , |
| | MENTIONS SHOWN ON AP E16.01, COMMENT |
| | HAD TO DO WITH CLUBHOUSE PLANS. |
| | COMMENT HAS NOT BEEN ADDRESSED, PLEASE |
| | SEE 700.12E. |
| | |
| | 3)NOTE: PLEASE SEE THE REVISED NEW |
| | SHEETS FOR APE16.02 WAS NOT SUBMITTED, |
| | OTHER REVISED RISER DIAGRAMS DID MAKE |
| | SOME OF THE CHANGES, BUT UNABLE TO |
| | VERIFY ON AP SHEET. |
| | 250.50 |
| | PLEASE ALSO SEE MIN SIZE OF CONDUCTORS |
| | FOR ALUM AND ALSO FOR GROUNDING/BONDING. |
| | 310.2 |
| | |
| | 4)NOTE: PLEASE SEE NOTE ON AP E16.02, |
| | STILL NOTES, RECEPTS TO BE ARC FAULT |
| | PROTECTED. IT HAS BEEN NOTED ON AP E-16. |
| | 01. |
| | |
| | 5)NOTE: PLEASE PROVIDE AWG ON PANEL |
| | SCHEDULES AND CORRELATE WITH OCP. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW SHEETS FOR 3 COMPLETE |
| | SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |