Notes
Date Text
2003-11-03 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
  
 1) SPECIFICATION "A" OR "B" SHALL BE IN-
 DICATED ON PLANS PER REQUIREMENT 7B OF
 THE FHA DESIGN MANUAL.
 2) SHT AP/P14.002 CLEANOUTS REQUIRED IN
 BLDG DRAIN PER SECTIONS 708.3.1, 708.3.3
 3) SHT AP/P14.04 SANT. RISERS 3S/P14.5,
 AND3SA/P14.5 TUBS NOT VENTED. 901.2
 4) SHT AP/P14.04 THE DISCHARGE PIPE
 SHALL NOT HAVE ANY TRAPPED SECTIONS AND
 SHALL HAVE A VISIBLE AIR GAP OR AIR GAP
 FITTING LOCATED IN THE SAME ROOM AS THE
 WATER HEATER.
 5) SHT AP/P14.04 WATER HEATER PIPING DE-
 TAIL, DIELECTRIC UNIONS NOT APPROVED FOR
 WATER PIPING. DELETE REFERENCE.
 6) AN RPZ BACKFLOW IS REQUIRED FOR EACH
 BLDG. SECTION 608.13.2
 7) SUBMIT A SANITARY ISOMETRIC BUILDING
 DRAIN. SHOW ALL PIPE SIZES AND SHOW ALL
 DFU'S AS THEY ACCUMULATE IN THE SYSTEM.
 SHOW C/O'S REQUIRED IN COMMENT #2. SEC
 104.3.1.1
 8) SHT AP/P14.05 WATER HEATER DETAIL.
 THERMAL EXPANSION CONTROL REQUIRED. IF
 530 VALVE IS USED FOR THIS PURPOSE, THE
 DRAINAGE LINE SHALL NOT BE CONNECTED TO
 THE PRESSURE/TEMP. RELIEF DISCHARGE LINE
 - ALSO EMERGENCY PAN SIZE SHALL COMPLY
 WITH SECTION 504.8.1.
 9) SUBMIT A WATER RISER DIAGRAM SHOWING
 HORIZONTAL PIPING WITH PIPE SIZES AND
 PIPING FOR TYPICAL UNITS SHOWING PIPE
 SIZES AND WATER HAMMER ARRESTORS REQUIR-
 ED BY SECTION 604.9. LOCATION OF WATER
 HAMMER ARRESTORS SHALL BE LOCATED NEAR
 THE FIXTURES IN AN "EFFECTIVE RANGE" NOT
 IN THE CEILING AS SHOWN. PDI-WH 201 AND
 MANUF. INST. INSTRUCT.
 10) FULL OPEN VALVES RQURED ON THE BASE
 OF EVERY WATER RISER PER SEC. 606.1(3),
 AND ON TOP OF EVERY WATER DOWN FEED PIPE
 PER SEC. 606.1(4). ACCESS WILL BE PRO-
 VIDED PER SEC. 606.3. PROVIDE DETAIL.
 11) SHTS CH/P14.01 & CH/P14.02 CLEANOUTS
 ARE REQUIRED NEAR THE BUILDING DRAIN AND
 BUILDING SEWER JUNCTION AND MAY BE TWO
 WAY TO CLEAN OUT BOTH BLDG. DRAIN AND
 BLDG. SEWER. SEC. 708.3.5
 12) SHT CH/P14.02 WATER RISER DIAGRAM.
 WATER HAMMERS SHALL BE LOCATED PER PDI-
 WH 201 AND MANUF. INSTALL. INSTRUCTIONS.
 13) AN RPZ BACKFLOW IS REQUIRED FOR
 CLUBHOUSE.
  