| 2003-11-03 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FHA-98 DESIGN MANUAL |
| | |
| | 1) SPECIFICATION "A" OR "B" SHALL BE IN- |
| | DICATED ON PLANS PER REQUIREMENT 7B OF |
| | THE FHA DESIGN MANUAL. |
| | 2) SHT AP/P14.002 CLEANOUTS REQUIRED IN |
| | BLDG DRAIN PER SECTIONS 708.3.1, 708.3.3 |
| | 3) SHT AP/P14.04 SANT. RISERS 3S/P14.5, |
| | AND3SA/P14.5 TUBS NOT VENTED. 901.2 |
| | 4) SHT AP/P14.04 THE DISCHARGE PIPE |
| | SHALL NOT HAVE ANY TRAPPED SECTIONS AND |
| | SHALL HAVE A VISIBLE AIR GAP OR AIR GAP |
| | FITTING LOCATED IN THE SAME ROOM AS THE |
| | WATER HEATER. |
| | 5) SHT AP/P14.04 WATER HEATER PIPING DE- |
| | TAIL, DIELECTRIC UNIONS NOT APPROVED FOR |
| | WATER PIPING. DELETE REFERENCE. |
| | 6) AN RPZ BACKFLOW IS REQUIRED FOR EACH |
| | BLDG. SECTION 608.13.2 |
| | 7) SUBMIT A SANITARY ISOMETRIC BUILDING |
| | DRAIN. SHOW ALL PIPE SIZES AND SHOW ALL |
| | DFU'S AS THEY ACCUMULATE IN THE SYSTEM. |
| | SHOW C/O'S REQUIRED IN COMMENT #2. SEC |
| | 104.3.1.1 |
| | 8) SHT AP/P14.05 WATER HEATER DETAIL. |
| | THERMAL EXPANSION CONTROL REQUIRED. IF |
| | 530 VALVE IS USED FOR THIS PURPOSE, THE |
| | DRAINAGE LINE SHALL NOT BE CONNECTED TO |
| | THE PRESSURE/TEMP. RELIEF DISCHARGE LINE |
| | - ALSO EMERGENCY PAN SIZE SHALL COMPLY |
| | WITH SECTION 504.8.1. |
| | 9) SUBMIT A WATER RISER DIAGRAM SHOWING |
| | HORIZONTAL PIPING WITH PIPE SIZES AND |
| | PIPING FOR TYPICAL UNITS SHOWING PIPE |
| | SIZES AND WATER HAMMER ARRESTORS REQUIR- |
| | ED BY SECTION 604.9. LOCATION OF WATER |
| | HAMMER ARRESTORS SHALL BE LOCATED NEAR |
| | THE FIXTURES IN AN "EFFECTIVE RANGE" NOT |
| | IN THE CEILING AS SHOWN. PDI-WH 201 AND |
| | MANUF. INST. INSTRUCT. |
| | 10) FULL OPEN VALVES RQURED ON THE BASE |
| | OF EVERY WATER RISER PER SEC. 606.1(3), |
| | AND ON TOP OF EVERY WATER DOWN FEED PIPE |
| | PER SEC. 606.1(4). ACCESS WILL BE PRO- |
| | VIDED PER SEC. 606.3. PROVIDE DETAIL. |
| | 11) SHTS CH/P14.01 & CH/P14.02 CLEANOUTS |
| | ARE REQUIRED NEAR THE BUILDING DRAIN AND |
| | BUILDING SEWER JUNCTION AND MAY BE TWO |
| | WAY TO CLEAN OUT BOTH BLDG. DRAIN AND |
| | BLDG. SEWER. SEC. 708.3.5 |
| | 12) SHT CH/P14.02 WATER RISER DIAGRAM. |
| | WATER HAMMERS SHALL BE LOCATED PER PDI- |
| | WH 201 AND MANUF. INSTALL. INSTRUCTIONS. |
| | 13) AN RPZ BACKFLOW IS REQUIRED FOR |
| | CLUBHOUSE. |
| | |