| Date |
Text |
| 2003-11-17 00:00:00 | DENIED: |
| | APARTMENTS: |
| | 1.PLEASE PROVIDE O.A. CALCULATIONS FOR |
| | THE DWELLING UNITS AS PER 2001 FBC(M) |
| | 403.3. |
| | |
| | 2.AUXILIARY DRAIN PAN REQUIRED WITH |
| | OVERFLOW PROTECTION OR A SEPARATE DRAIN |
| | LINE PER 2001 FBC(M) 307.2.3. |
| | |
| | 3.PLEASE NOTE, RETURN AIR GRILLES TO |
| | BE SIZED AS FOLLOWS - 50 SQ IN (OF |
| | GRILLE AREA) TO 100 CFM OF SUPPLY AIR |
| | WHEN SIZING THROUGH THE WALL TRANSFER |
| | GRILLES. 2001 FBC(M) 601.4 EXCEPTION #2. |
| | |
| | 4.PLAN SHEET 15.01 NOTE #12, SEE DRYER |
| | DUCT ROUTING AND CONNECTION ON THE ARCH |
| | PLANS.PLEASE INDICATE ARCH PLAN SHEET |
| | FOR QUICK REFERENCE. PLAN SHEET AP A1.06 |
| | SHOWS A DETAIL & AP A7.01 SHOWS THE |
| | TERMINATION AT OUTSIDE WALL WITH CAP. |
| | PLEASE NOTE IF SPECIFIC DRYERS ARE TO |
| | BE INSTALLED FOR THE CAPABILITY OF |
| | LONGER DUCT RUNOUTS, PROVIDE SUBMITTAL |
| | ON DRYER & DRYERS MUST BE INSTALLED |
| | PRIOR TO FINAL INSPECTION. |
| | |
| | CLUBHOUSE: |
| | 1. AS PER 2001 FBC(M) 601.4 EXCEPTION |
| | #1 TRANSFER DUCTS SHALL BE SIZED 1 1/2 |
| | TIMES THE CROSS SECTIONAL AREA (SQ IN) |
| | OF THE SUPPLY ENETERING THE ROOM OR |
| | SPACE.SEE ATTACHED. |
| | |
| | 2.PLAN SHEET CH M15.01 INDICATES R/A |
| | GRILLES AS "E".PLAN SHEET CH M15.02 |
| | GRILLE & DIFFUSER SCHEDULE INDICATES |
| | RETURNS AS "B".PLEASE CLARIFY |
| | |
| | 3.PLAN SHEET CH M-15.01 INDICATES A |
| | TRANSFER DUCT FROM THE LAUNDRY ROOM TO |
| | THE CLUBROOM.ROOMS THAT EMIT HEAT OR |
| | EQUIPMENT OR PROCESSES THAT PRODUCE OR |
| | THROW OFF DUST OR PARTICLES LIGHT ENOUGH |
| | TO FLOAT IN THE AIR SHALL NOT BE RE- |
| | CICULATED. 2001 FBC(M) 401.7 & 502.1. |
| | |
| | 4.DRYER INSTALLATIONS EXHAUSTING MORE |
| | THAN 200 CFM SHALL BE PROVIDED WITH MAKE |
| | UP AIR. 2001 FBC(M) 504.5. |
| | |
| | MAINTENANCE BUILDING: |
| | 1.PLEASE INDICATE WHAT TYPE MAITENANCE |
| | WILL BE DONE IN THIS AREA.WORKING ON |
| | VECHICLES, MACHINES (COMBUSTION ENGINES) |
| | LAWN EQUIPMENT? |
| | |
| | 2.PROVIDE OUTSIDE AIR CALCULATIONS. |
| | |
| | 3.INDICATE IF THE OFFICE IN THE |
| | MAINTENANCE BUILDING WILL BE OCCUPIED |
| | FULL TIME PART TIME?PLEASE CLARIFY. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561) 805-6719. |