| Date |
Text |
| 2003-10-23 00:00:00 | ************** UNSAT **************** |
| | |
| | 1)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH THE SUBMITTED |
| | PANEL SCHEDULES. |
| | PLEASE SEE 700.12 FOR CIRCUITING OF |
| | EM/EXT LTS. |
| | |
| | 2)NOTE: PLEASE CLARIFY LIGHTING IN ELEC |
| | RM PER 700.16 |
| | |
| | 3)NOTE: PLEASE SEE SERVICE SHOWN ON |
| | PLAN LAYOUT. SHOWS FPL TRANSFORMER |
| | MOUNTED IN BETWEEN METER AND MAINS? |
| | PLEASE CORRELATEWITH RISER. |
| | |
| | 4)NOTE: PLEASE INCLUDE FOOTER STEEL |
| | AS PART OF THE GROUNDING ELECTRODE |
| | SYSTEM AS REQ'D PER 250.50. THIS IS FOR |
| | THE MAINT BLDG AND CLUBHOUSE. |
| | |
| | 5)NOTE: PLEASE SEE PANEL SCHEDULE FOR |
| | PANEL "A", SHOWN AS MCB AND RISER SHOWS |
| | MLO. PLEASE CORRELATE. A MCB IS PERMITT- |
| | -EDBU T NOT REQ'D. IF SHOWN THEN IT |
| | WILL BE REQ'D TO BE INSTALLED. |
| | |
| | 6)NOTE: PLEASE INCREASE SEC'S TO NEXT |
| | SIZE UP. NEXT SIZEUP FOR SEC'S WOULD |
| | BE 700A (240.6) AND SERVICE IS SHOWN |
| | AS BEING "800A'S". 240.42,230.43, SIZE |
| | PER 310.16 |
| | |
| | 7)NOTE: PLEASE PROVIDEAIC RATINGS FOR |
| | ALL SERVICE EQUIPMENT. MAINS/ PANELS/ |
| | BRKRS ARE ALL TO BE RATED FOR THE |
| | AVAILABLE FAULT CURRENT. 110.9 |
| | PLEASE ALSO INCLUDE FOR EQUIP ON E16.01 |
| | |
| | 8)NOTE: PLEASE SEE THAT MAIL KIOSK WILL |
| | REQUIRE A MEANS OF DISC PER 225.31 |
| | |
| | 9)NOTE:PLEASE SEE MISSING SDE'S INSIDE |
| | AND OUTSIDE ALL SLEEPING RMS. NFPA-72 |
| | 8-1.4.2 |
| | |
| | 10)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | APTS UNITS ALSO AND CORRELATE. |
| | |
| | 11)NOTE: PLEASE SHOW ALL CONTINUOUS LOAD |
| | -S AT 125%. 215.3/230.42 ETC |
| | |
| | 12)NOTE: PLEASE NOTE, PER LOCAL AMEND- |
| | -MENTS. ALUMINUM CONDUCTORS ARE NOT TO |
| | BE USED FOR GROUNDING OR BONDING.310.2 |
| | NONE SMALLER THAN #2 FOR ALL OTHERS. |
| | |
| | 13)NOTE: PLEASE SEE 250.50 FOR REQ'D |
| | ATTACHMENTS FOR GROUNDING ELECTRODE |
| | SYSTEM. |
| | |
| | 14)NOTE: PLEASE SEE NOTE ON PLAN MENTION |
| | (S) TO PROTECT BEDROOM RECEPTS FOR ARC |
| | FAULT. PER 210.12 |
| | PLEASE SEE THAT WE ARE NOW UNDER THE |
| | 2002 NEC AND REQUIREMENTS FOR 210.12 |
| | HAS CHANGED. |
| | |
| | 15)NOTE: PLEASE PROVIDE WIRE SIZES ON |
| | PANEL SCHEDULE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | PLEASE SEE NOTES FROM OTHER REVIEWERS |
| | AS COMMENTS MAY AFFECT ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | INSERT NEW SHEETS INTO COMPLETE SETS |
| | FOR REVIEW AND STAMPING. |
| | |