Plan Review Notes
Plan Review Notes For Permit 03100653
Permit Number 03100653
Review Stop E
Sequence Number 1
Notes
Date Text
2003-10-23 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULES.
 PLEASE SEE 700.12 FOR CIRCUITING OF
 EM/EXT LTS.
  
 2)NOTE: PLEASE CLARIFY LIGHTING IN ELEC
 RM PER 700.16
  
 3)NOTE: PLEASE SEE SERVICE SHOWN ON
 PLAN LAYOUT. SHOWS FPL TRANSFORMER
 MOUNTED IN BETWEEN METER AND MAINS?
 PLEASE CORRELATEWITH RISER.
  
 4)NOTE: PLEASE INCLUDE FOOTER STEEL
 AS PART OF THE GROUNDING ELECTRODE
 SYSTEM AS REQ'D PER 250.50. THIS IS FOR
 THE MAINT BLDG AND CLUBHOUSE.
  
 5)NOTE: PLEASE SEE PANEL SCHEDULE FOR
 PANEL "A", SHOWN AS MCB AND RISER SHOWS
 MLO. PLEASE CORRELATE. A MCB IS PERMITT-
 -EDBU T NOT REQ'D. IF SHOWN THEN IT
 WILL BE REQ'D TO BE INSTALLED.
  
 6)NOTE: PLEASE INCREASE SEC'S TO NEXT
 SIZE UP. NEXT SIZEUP FOR SEC'S WOULD
 BE 700A (240.6) AND SERVICE IS SHOWN
 AS BEING "800A'S". 240.42,230.43, SIZE
 PER 310.16
  
 7)NOTE: PLEASE PROVIDEAIC RATINGS FOR
 ALL SERVICE EQUIPMENT. MAINS/ PANELS/
 BRKRS ARE ALL TO BE RATED FOR THE
 AVAILABLE FAULT CURRENT. 110.9
 PLEASE ALSO INCLUDE FOR EQUIP ON E16.01
  
 8)NOTE: PLEASE SEE THAT MAIL KIOSK WILL
 REQUIRE A MEANS OF DISC PER 225.31
  
 9)NOTE:PLEASE SEE MISSING SDE'S INSIDE
 AND OUTSIDE ALL SLEEPING RMS. NFPA-72
 8-1.4.2
  
 10)NOTE: PLEASE SHOW ALL CIRCUITING ON
 APTS UNITS ALSO AND CORRELATE.
  
 11)NOTE: PLEASE SHOW ALL CONTINUOUS LOAD
 -S AT 125%. 215.3/230.42 ETC
  
 12)NOTE: PLEASE NOTE, PER LOCAL AMEND-
 -MENTS. ALUMINUM CONDUCTORS ARE NOT TO
 BE USED FOR GROUNDING OR BONDING.310.2
 NONE SMALLER THAN #2 FOR ALL OTHERS.
  
 13)NOTE: PLEASE SEE 250.50 FOR REQ'D
 ATTACHMENTS FOR GROUNDING ELECTRODE
 SYSTEM.
  
 14)NOTE: PLEASE SEE NOTE ON PLAN MENTION
 (S) TO PROTECT BEDROOM RECEPTS FOR ARC
 FAULT. PER 210.12
 PLEASE SEE THAT WE ARE NOW UNDER THE
 2002 NEC AND REQUIREMENTS FOR 210.12
 HAS CHANGED.
  
 15)NOTE: PLEASE PROVIDE WIRE SIZES ON
 PANEL SCHEDULE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 PLEASE SEE NOTES FROM OTHER REVIEWERS
 AS COMMENTS MAY AFFECT ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT NEW SHEETS INTO COMPLETE SETS
 FOR REVIEW AND STAMPING.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW