| 2003-11-24 00:00:00 | PLAN REVIEW ONLY, NOT A PERMIT |
| | APPLICATION.AT TIME OF PERMIT |
| | APPLICATION THE FOLLOWING COMMENTS MAY |
| | BE ADDRESSED ON THE PLANS. |
| | |
| | DUE TO THE SCOPE AND NATURE OF THE |
| | PROPOSED WORK THE BUILDING OFFICIAL |
| | WILL REQUIRE A RESIDENT INSPECTOR AS |
| | PROVIDED FOR IN FBC 105.3 AS AMENDED BY |
| | THE CITY OF WEST PALM BEACH.CONTACT |
| | HAROLD PISKURA AT 561-805-6665 FOR MORE |
| | INFORMATION. |
| | |
| | SHEET A1.03 DOES NOT CITE THE CORRECT |
| | EDITION OF THE STANDARDS INVOKED BY THE |
| | 2001 FBC.EXAMPLE, ACI 318-02 NOT THE |
| | 1995 EDITION.PLEASE REVISE AND ENSURE |
| | COMPLIANCE AS NECESSARY, INCLUDING |
| | CONCRETE COVERAGE AND LAP.SEE FBC |
| | 3500. |
| | |
| | THE CITY OF WEST PALM BEACH HAS AMENDED |
| | FBC TABLE -2307.6B.THE MINIMUM |
| | THICKNESS STRUCTURAL PANEL IS 19/32" |
| | FOR 16" OC SPACING, NOT THE DECLARED |
| | 7/16".SEE ALSO FBC 2301.1.2 AND THE |
| | 100 MPH LIMITATION WITH REGARDS TO THE |
| | NAILINGSCHEDULE ON SHEET A1.03 NOTE |
| | #10. |
| | |
| | SHEET A1.05. THE NER -459 REPORT FOR |
| | THE MAGNA WALL SHOWN IS EXPIRED. |
| | PROVIDE AN ACCEPTANCE REPORT SUITABLE |
| | FOR THE FBC. |
| | |
| | THE BATH EXHAUST PENETRATION DETAIL ON |
| | SHEET A1.06 AND DETAIL 3/A7.03 IS NOT |
| | AN ACCEPTABLE ALTERNATE METHOD UNDER |
| | FBC 103.7 GIVEN THE 30 GA DUCT |
| | MATERIAL.PLEASE PROVIDE A FIRE RATED |
| | SHAFT ENCLOSLURE COMPLYING WITH FBC 705. |
| | 2.2. |
| | |
| | SHEET A2.01.PLEASE PROVIDE DIMENSIONS |
| | ON THE SITE PLANS SHOWING THE DISTANCE |
| | BETWEEN BUILDINGS AND PROPERTY LINES. |
| | ALSO SHOW THE PERITNENT TOPOGRAPHIC |
| | FEATURES SOTHAT HANDI CAP ACCESSIBILITY |
| | MAY BE DETERMINED. |
| | |
| | THE PLANS AS SHOWN DO NOT MEET THE |
| | MINIMUM EGRESS REQUIREMENTS.FBC |
| | 1004.1.4 REQUIRES THE EXITS TO BE A |
| | DISTANCE APART EQUAL TO OR GREATER THAN |
| | 1/2 THE DIAGONAL DISTANCE SERVED.TWO |
| | INDEPENDENT EXITS ARE REQUIRED FROM THE |
| | THIRD FLOOR, SEE FBC 1004.2.1 AND |
| | 1026.1.1, #4. |
| | |
| | THE STAIRS ARE REQUIRED TO BE ENCLOSED |
| | IN FIRE RATED CONSTRUCTION, SEE FBC |
| | 1006.1.THEY DO NOT MEET THE CRITERIA |
| | FOR ESXTERIOR STAIRS IN FBC 1006.2 AND |
| | FBC 1014.SEE ALSO, FBC 1007.1.2 RE: |
| | CLOSED RISERS. |
| | |
| | SHEET A7.02, SHOW A SPECIFIC METHOD FOR |
| | INSTALLATION OF THE FIRE BLOCKING. DO |
| | NOT QUOTE THE CODE SECTION, SEE FBC 104. |
| | 2.1. |
| | |
| | SEE FBC 1608.2 FOR THE MINIMUM DESIGN |
| | LOADS FOR HAND AND GUARD RAILS. |
| | |
| | SHOW THE FIRE SPRINKLER DESIGN ON THE |
| | PERMIT PLANS, INCLUDE THE MINIMUM |
| | INFORMATION IN CHAPTER TWO OF NFPA |
| | 13R-99. |
| | |
| | BEFORE A PERMIT TO CONSTRUCT MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO THE |
| | COUNTY, THE PERMIT PLANS STAMPED BY |
| | THAT OFFICE AND A COPY OF THE PAID |
| | RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. |
| | |
| | SEPARATE PERMITS WILL BE REQUIRED FOR |
| | EACH STRUCTURE. |
| | |
| | IF NOTICE OF ACCEPTANCE REPORTS ARE NOT |
| | INCLUDED FOR THE DOORS, WINDOWS AND ROOF |
| | COVERINGS, SEPARATE PERMIT INFORMATION |
| | AND FEES WILL BE REQUIRED. |