Plan Review Notes
Plan Review Notes For Permit 03100653
Permit Number 03100653
Review Stop B
Sequence Number 1
Notes
Date Text
2003-11-24 00:00:00PLAN REVIEW ONLY, NOT A PERMIT
 APPLICATION.AT TIME OF PERMIT
 APPLICATION THE FOLLOWING COMMENTS MAY
 BE ADDRESSED ON THE PLANS.
  
 DUE TO THE SCOPE AND NATURE OF THE
 PROPOSED WORK THE BUILDING OFFICIAL
 WILL REQUIRE A RESIDENT INSPECTOR AS
 PROVIDED FOR IN FBC 105.3 AS AMENDED BY
 THE CITY OF WEST PALM BEACH.CONTACT
 HAROLD PISKURA AT 561-805-6665 FOR MORE
 INFORMATION.
  
 SHEET A1.03 DOES NOT CITE THE CORRECT
 EDITION OF THE STANDARDS INVOKED BY THE
 2001 FBC.EXAMPLE, ACI 318-02 NOT THE
 1995 EDITION.PLEASE REVISE AND ENSURE
 COMPLIANCE AS NECESSARY, INCLUDING
 CONCRETE COVERAGE AND LAP.SEE FBC
 3500.
  
 THE CITY OF WEST PALM BEACH HAS AMENDED
 FBC TABLE -2307.6B.THE MINIMUM
 THICKNESS STRUCTURAL PANEL IS 19/32"
 FOR 16" OC SPACING, NOT THE DECLARED
 7/16".SEE ALSO FBC 2301.1.2 AND THE
 100 MPH LIMITATION WITH REGARDS TO THE
 NAILINGSCHEDULE ON SHEET A1.03 NOTE
 #10.
  
 SHEET A1.05. THE NER -459 REPORT FOR
 THE MAGNA WALL SHOWN IS EXPIRED.
 PROVIDE AN ACCEPTANCE REPORT SUITABLE
 FOR THE FBC.
  
 THE BATH EXHAUST PENETRATION DETAIL ON
 SHEET A1.06 AND DETAIL 3/A7.03 IS NOT
 AN ACCEPTABLE ALTERNATE METHOD UNDER
 FBC 103.7 GIVEN THE 30 GA DUCT
 MATERIAL.PLEASE PROVIDE A FIRE RATED
 SHAFT ENCLOSLURE COMPLYING WITH FBC 705.
 2.2.
  
 SHEET A2.01.PLEASE PROVIDE DIMENSIONS
 ON THE SITE PLANS SHOWING THE DISTANCE
 BETWEEN BUILDINGS AND PROPERTY LINES.
 ALSO SHOW THE PERITNENT TOPOGRAPHIC
 FEATURES SOTHAT HANDI CAP ACCESSIBILITY
 MAY BE DETERMINED.
  
 THE PLANS AS SHOWN DO NOT MEET THE
 MINIMUM EGRESS REQUIREMENTS.FBC
 1004.1.4 REQUIRES THE EXITS TO BE A
 DISTANCE APART EQUAL TO OR GREATER THAN
 1/2 THE DIAGONAL DISTANCE SERVED.TWO
 INDEPENDENT EXITS ARE REQUIRED FROM THE
 THIRD FLOOR, SEE FBC 1004.2.1 AND
 1026.1.1, #4.
  
 THE STAIRS ARE REQUIRED TO BE ENCLOSED
 IN FIRE RATED CONSTRUCTION, SEE FBC
 1006.1.THEY DO NOT MEET THE CRITERIA
 FOR ESXTERIOR STAIRS IN FBC 1006.2 AND
 FBC 1014.SEE ALSO, FBC 1007.1.2 RE:
 CLOSED RISERS.
  
 SHEET A7.02, SHOW A SPECIFIC METHOD FOR
 INSTALLATION OF THE FIRE BLOCKING. DO
 NOT QUOTE THE CODE SECTION, SEE FBC 104.
 2.1.
  
 SEE FBC 1608.2 FOR THE MINIMUM DESIGN
 LOADS FOR HAND AND GUARD RAILS.
  
 SHOW THE FIRE SPRINKLER DESIGN ON THE
 PERMIT PLANS, INCLUDE THE MINIMUM
 INFORMATION IN CHAPTER TWO OF NFPA
 13R-99.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO THE
 COUNTY, THE PERMIT PLANS STAMPED BY
 THAT OFFICE AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.
  
 SEPARATE PERMITS WILL BE REQUIRED FOR
 EACH STRUCTURE.
  
 IF NOTICE OF ACCEPTANCE REPORTS ARE NOT
 INCLUDED FOR THE DOORS, WINDOWS AND ROOF
 COVERINGS, SEPARATE PERMIT INFORMATION
 AND FEES WILL BE REQUIRED.