| Plan Review Notes For Permit 03100635 |
| Permit Number |
03100635 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-10-30 00:00:00 | ************PROVISO********************* | | | NOTE #13 ON SHEET E-2 SHOULD READ HVAC | | | DUCT DETECTOR SHALL INITIATE A FIRE | | | ALARM NOT A SUPERVISORY. SEPARATE PLANS | | | AND PERMITS ARE REQUIRED FOR FIRE ALARM | | | AND FIRE SPRINKLER SYSTEMS REMODEL. | | | | | | NATE MCCRAY, CAPTAIN | | | 805-6722 OR 835-2910 |
|