2003-12-08 00:00:00*************** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT ALL ELECTRICAL
 REVISIONS UNDER ELECTRICAL PERMIT AS
 REVIEW WAS NOT DONE UNDER THIS PERMIT
 AS PER REQUEST BY OWNER/ARCH.
  
 2)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN TO SUB
 PANELS. 250.110/250.122/250.24
  
 3)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 AND PLEASE SHOW ALL EM/EXT LTS PER
 700.12E
  
 4)NOTE: PLEASE SIZE GEC PER 250.66.
  
 5)NOTE: PLEASE SEE FS 471.025 AND FAC
 61G15-23.002. PLANS ARE REQ'D TO HAVE
 A COMPLETE SIGNATURE BY ENG OF RECORD.
 INITIALS ARE NOT ACCEPTABLE PER THE
 ABOVE AND DIRECTION FROM FL BOARD OF PE.
 'S.
  
 6)NOTE: PLEASE SUBMIT AIC RATING FOR ALL
 NEW EQUIPMENT BEING INSTALL. MAINS/ BRKR
 'S/ AND PANELS ARE ALL TO BE RATED FOR
 THE AVAILABLE FAULT CURRENT. 110.9/215.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REIVEW 561-805-6717