| Plan Review Notes For Permit 03100621 |
| Permit Number |
03100621 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2003-12-08 00:00:00 | *************** UNSAT *************** | | | | | | 1)NOTE: PLEASE SUBMIT ALL ELECTRICAL | | | REVISIONS UNDER ELECTRICAL PERMIT AS | | | REVIEW WAS NOT DONE UNDER THIS PERMIT | | | AS PER REQUEST BY OWNER/ARCH. | | | | | | 2)NOTE: PLEASE SEE MISSING EQUIPMENT | | | GROUNDING CONDUCTOR FROM MAIN TO SUB | | | PANELS. 250.110/250.122/250.24 | | | | | | 3)NOTE: PLEASE SEE FIRE REVIEW COMMENTS | | | AND PLEASE SHOW ALL EM/EXT LTS PER | | | 700.12E | | | | | | 4)NOTE: PLEASE SIZE GEC PER 250.66. | | | | | | 5)NOTE: PLEASE SEE FS 471.025 AND FAC | | | 61G15-23.002. PLANS ARE REQ'D TO HAVE | | | A COMPLETE SIGNATURE BY ENG OF RECORD. | | | INITIALS ARE NOT ACCEPTABLE PER THE | | | ABOVE AND DIRECTION FROM FL BOARD OF PE. | | | 'S. | | | | | | 6)NOTE: PLEASE SUBMIT AIC RATING FOR ALL | | | NEW EQUIPMENT BEING INSTALL. MAINS/ BRKR | | | 'S/ AND PANELS ARE ALL TO BE RATED FOR | | | THE AVAILABLE FAULT CURRENT. 110.9/215.5 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REIVEW 561-805-6717 | | | [email protected] | | | 561-805-6717 |
|