| Plan Review Notes For Permit 03100621 |
| Permit Number |
03100621 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-10-17 00:00:00 | 1) FIRE PROTECTION BACKFLOW DEVICE | | | IS REQUIRED TO BE EQUIPPED WITH | | | TAMPER SWITCHES, CHAIN AND LOCK. | | | | | | 2) FIRE HYDRANT DETAIL SHOWS BOLLARD | | | BEHIND FIRE HYDRANT. NO ITEMS ALLOWED | | | WITHIN 4 FEET TO THE REAR OF FIRE | | | HYDRANT. NEW FIRE HYDRANT SHALL MEET | | | FIRE RESCUE AND UTILITY STANDARDS. | | | PLEASE OBTAIN CITY DETAILS. | | | | | | 3) ALL FIRE SPRINKLER SYSTEMS ARE | | | REQUIRED TO BE MONITORED BY UL LISTED | | | FOR CENTRAL STATION SERVICE. | | | | | | 4) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR FIRE SPRINKLER SYSTEM. | | | | | | 5) NO ILLUMINATED EXIT SIGNS OR | | | EMERGENCY LIGHTS SHOWN ON PLANS. | | | | | | 6) MODULAR UNIT LOCATED IN FIRE LIMITS. | | | SEE CBAA CASE # 1247. | | | | | | 7) BUILDING ADDRESS REQUIRED. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|