Notes
Date Text
2003-10-22 00:00:00FBC 1804.1.3 REQUIRES THE BOTTOM OF
 FOUNDATIONS TO BE AT LEAST 12" BELOW
 GRADE. SHEET 4 OF 4 OF THE RESUN
 LEASING/BODZIAK PLANS SHOWS THE PIERS
 ON TOP OF GRADE. PLEASE REVISE AS
 NECESSARY.
  
 ALSO, SHOW THE TOPOGRAPHY TO PROVIDE
 THESLOPING DRAINAGE IN ACCORDANCE WITH
 FBC 1804.1.7.
  
 SHOW THE METHOD OF TERMITE PROTECTION
 AS REQUIRED BY FBC 1816.
  
 SHEETS 1 AND 2 OF 6 ARE MISSING FROM
 THEEDUARDO VAZQUEZ, PE PLANS.
  
 SHEET 3 OF 6 OF THE VAZQUEZ PLANS SHOWS
 STRUCTURAL ALTERATIONS TO THE EXTERIOR
 WALLS OF THE BUILDING THAT WILL
 INVALIDATE THE DCA INSIGNIA AND MANDATE
 COMPLIANCE WITH THE CURRENT FBC.
  
 GIVEN THE ABOVE, PROVIDE DETAILS FOR
 THEINSTALLATION OF THE NEW DOORS AND
 WINDOWS, HURRICANE MISSLE IMPACT
 PROTECTION, AND TEST AND NOTICE OF
 ACCEPTANCE REPORTS.PROVIDE STRUCTURAL
 CALCULATIONS DEMONSTRATINGCOMPLIANCE
 WITH THE FBC FOR A 140 MPH WIND REGION.
  
 PROVIDE DETAILS FOR THE PLUMBING AND
 ELECTRICAL FOR THE NEW KITCHENETTE AREA
 AND THE ADDED PARTITIONS.
  
 THE FOLLOWING REGARDS THE PROPOSED
 PATIO, RAMP AND STAIR CONSTRUCTION.
  
 PLEASE PROVIDE STRUCTURAL CALCULATIONS
 FOR THE 2X2 GUARD RAIL AND 3/4" PICKETS
 SHOWN IN SECTIONS 4/P4 AND 5/P4.SEE
 FBC 1608.2 FOR MINIMUM DESIGN LOADS.
  
 SHOW THE STAIR TREAD AND RISER
 DIMENSIONS. SEE FBC 1007.2 AND 1007.3.
  
 HANDRAILS ARE REQUIRED ON BOTH SIDES OF
 STAIRS, EAST ELEVATION, FBC 1007.5.2
 ANDWITHIN 30" OF EGRESS STAIR WIDTH,
 1007. 5.7.PLEASE REVISE AS NECESSARY.
  
 SHEET 5 OF 6.PLEASE PROVIDE THE FIRE
 SPRINKLER DESIGN INFORMATION AS
 PROVIDED FOR IN NFPA 13-99 CHAPTER 8;
 AND CHAPTER 61G15-32 OF THE FL
 ADMINISTRATIVE CODE.
  
 THE DECLARED PERMIT VALUATION OF
 $20,000.00 IS TOO LOW FOR THE SCOPE OF
 WORK DECLARED ON SHEET 3 OF 6 OF THE
 VAZQUEZ PLANS.PLEASE PROVIDE A SIGNED
 CONTRACT(S) ANDDETAILED TAKEOFFS,
 INCLUDING EXTENSIONS, TO ESTABLISH THE
 ACTUAL COSTS OF THE WORK FOR THIS
 PERMIT.