| Plan Review Notes For Permit 03100590 |
| Permit Number |
03100590 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-10-14 00:00:00 | ************ UNSAT ****************** | | | | | | 1)NOTE: PLEASE SHOW CIRCUITING ON PLANS | | | AND CORRELATE WITH SUBMITTED PANEL | | | SCHEDULE. UNABLE TO VERIFY AT THIS TIME | | | IF CIRCUITS ARE SEPARATED FOR SUITES AS | | | REQ'D. 215.5 | | | | | | 2)NOTE: PLEASE SEE THAT EM/EXT LTS | | | APPEAR TO COMING FROM ONE PANEL ONLY? | | | PLEASE CIRCUIT EM/EXT LTS OER 700.12E | | | | | | 3)NOTE: PLEASE SHOW TRK LOADS PER 220.12 | | | B. | | | | | | 4)NOTE: PLEASE CLARIFY NOTE ON PANEL | | | SCHEDULE. NOTE MENTIONS, RELOCATE LTS TO | | | NEW TRANSFORMER LOCATIONS? PLEASE SEE | | | THAT THERE IS NOTHING SHOWN ON PLANS FOR | | | THIS?? | | | | | | PLEASE SEE NOTES FROM OTHER REVIEWERS | | | THAT MAY HAVE AN AFFECT ON ELECTRICAL | | | PLANS. | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | INSERT NEW SHEETS INTO TWO COMPLETE SETS | | | FOR REVIEW AND STAMPING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|