| Plan Review Notes For Permit 03100577 |
| Permit Number |
03100577 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-10-15 00:00:00 | PLEASE CLARIFY THE FOLLOWING INFORMATION | | | | | | 1.SHOULD STAIRWELL HAVE A FIRE RATING, | | | FIRE DAMPER REQUIRED. | | | | | | 2.PLEASE NOTE FRESH AIR INTAKE SHALL | | | BE A MINIMUM OF 10 FT FROM EXHAUST | | | OUTLET. | | | | | | 3.DUCT SMOKE DETECTORS ARE REQUIRED | | | FOR A SINGLE UNIT GREATER THAN 2,000 | | | CFM OR ON UNITS THAT SUPPLY AND RETURN | | | AIR INTERMINGLE. | | | | | | 4.PIPING TO CHILLER/PUMPS SHALL BE | | | SUBMITTED PRIOR TO INSPECTION. | | | | | | 5.PLEASE INDICATE CONDENSATE DRAIN | | | PIPE (LAYOUT, MATERIAL, SIZE & DISPOSAL) | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|