| 2004-01-30 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6716 |
| | E-MAIL: [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | FOR CONSISTENCY, THE FOLLOWING COMMENTS |
| | ARE NUMBERED AS PER THE BUILDING PLAN |
| | REVIEW OF 12/19/03: |
| | |
| | 1) THIS COMMENT HAS NOT BEEN ADDRESSED. |
| | THE RESPONSE LETTER DATED 1/15/04 IS |
| | FROM R.C.T. ENGINEERING.THE COMMENT IS |
| | ABOUT THE ARCHITECTURAL PLANS SEALED BY |
| | THE ARCHITECT AND SHOULD HAVE BEEN |
| | ADDRESSED BY STEPHEN BORUFF, ARCHITECT'S |
| | AND PLANNERS INC.THE LICENSE NUMBER |
| | PRINTED ON SHEETS A-1 THROUGH A-11 IS |
| | THAT OF THE ARCHITECTURAL BUSINESS ONLY. |
| | PLANS PREPARED BY A REGISTERED ARCHITECT |
| | SHALL INCLUDE THE PRINTED NAME AND |
| | LICENSE NUMBER OF THE ARCHITECT SEALING |
| | THE PLANS, NOT JUST THE ARCHITECTURAL |
| | BUSINESS.FOR YOUR REFERENCE THE |
| | FOLLOWING IS A SUMMARY EXTRACT FROM THE |
| | FLORIDA ADMINISTRATIVE CODE: |
| | 61G1-16.004FL. ADMIN. CODE. - PLANS |
| | PREPARED BY A REGISTERED ARCHITECT |
| | SHALL INCLUDE A TITLE BLOCK WHICH MUST: |
| | - STATE THE FIRM NAME, ADDRESS AND |
| | TELEPHONE NUMBER |
| | - STATE THE FIRM LICENSE NUMBER |
| | - STATE PROJECT NAME OR IDENTIFICATION |
| | - STATE DATE PREPARED |
| | - INCLUDE AN ORIGINAL SIGNATURE AND |
| | DATED SEAL |
| | - INCLUDE THE PRINTED NAME OF THE |
| | ARCHITECT SEALING THE PLANS |
| | ADD THE PRINTED NAME AND LICENSE NUMBER |
| | OF THE ARCHITECT ON SHEETS A-1 THRU A-11 |
| | |
| | 8) PRODUCT APPROVALS. |
| | (A) WALL/ROOF PANELS, A VALID PRODUCT |
| | APPROVAL OR SITE SPECIFIC ENGINEERING IS |
| | REQUIRED FOR THE PANEL SYSTEM BEFORE A |
| | PERMIT IS ISSUED. |
| | (B) WINDOWS AND DOORS, SUBMITTAL OF A |
| | PRODUCT APPROVAL FOR ROLL-UP DOORS IS |
| | ACKNOWLEDGED BUT NO VALID PRODUCT |
| | APPROVAL HAS BEEN SUBMITTED FOR THE |
| | WINDOWS AND EXTERIOR DOORS.SEPARATE |
| | PERMIT APPLICATIONS WILL BE REQUIRED. |
| | NOTE: FL. ADMIN CODE RULE 9B-72 (IN |
| | EFFECT SINCE OCTOBER 1, 2003) REQUIRES |
| | THAT PRODUCTS HAVE STATEWIDE, LOCAL OR |
| | SITE-SPECIFIC PRODUCT APPROVAL.THE |
| | SUBMITTAL SHOULD INCLUDE THE STATEWIDE |
| | PRODUCT APPROVAL NUMBER (FL###), |
| | AVAILABLE FROM THE DEPT OF COMMUNITY |
| | AFFAIRS PRODUCT APPROVAL WEBSITE |
| | WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | TELEPHONE: (561) 805 6716ROBERT BROWN |
| | E-MAIL: [email protected] |