| Plan Review Notes For Permit 03100570 |
| Permit Number |
03100570 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-10-21 00:00:00 | DENIED | | | REFERENCE: FLORIDA ADMINISTRATIVE CODE | | | | | | 1) G6G15-23.002(2) SEE ATTACHED SHEET | | | CONCERNING INFORMATION REQUIRED ON TITLE | | | BLOCK. | | | 2) SHT P-4 SANITARY RISER DIAGRAM, THE | | | TRAPS ON MANY FIXTURES SHOW "S" TRAPS. | | | TRAPS SHALL BE VENTED AS SHOWN BY RED | | | LINE CORRECTIONS. PLEASE SHOW PROPER | | | VENTS. 1002.3(5) | | | 3) WATER SERVICE TO BLDG SHALL HAVE | | | BACKFLOW PREVENTIONS. 608.13.2 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|