Plan Review Notes
Plan Review Notes For Permit 03100570
Permit Number 03100570
Review Stop P
Sequence Number 1
Notes
Date Text
2003-10-21 00:00:00DENIED
 REFERENCE: FLORIDA ADMINISTRATIVE CODE
  
 1) G6G15-23.002(2) SEE ATTACHED SHEET
 CONCERNING INFORMATION REQUIRED ON TITLE
 BLOCK.
 2) SHT P-4 SANITARY RISER DIAGRAM, THE
 TRAPS ON MANY FIXTURES SHOW "S" TRAPS.
 TRAPS SHALL BE VENTED AS SHOWN BY RED
 LINE CORRECTIONS. PLEASE SHOW PROPER
 VENTS. 1002.3(5)
 3) WATER SERVICE TO BLDG SHALL HAVE
 BACKFLOW PREVENTIONS. 608.13.2
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]