2003-11-14 00:00:00DENIED:
 1.PLEASE NOTE PLAN SHEET AC-2 NOTE 6
 E REFERS TO PLAN SHEET FP-2. PLAN NOT
 SUBMITTED.
  
 2.PLEASE PROVIDE ELEVATION FOR THE
 TERMINATION OF THE EXHAUST HOOD THROUGH
 THE SIDE WALL.TERMINATION SHALL COMPLY
 WITH 2001 FBC(M) 506.3.14.2 & 506.3.14.3
  
 3.PLANS DO NOT INCLUDE ANY INFORMATION
 ON THE HOOD OR FIRE SUPPRESSION SYSTEM.
 PLEASE PROVIDE MANUFACTURER SUBMITTAL
 DATA AND ALL PERTINENT INFORMATION WITH
 PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.