| Plan Review Notes For Permit 03100570 |
| Permit Number |
03100570 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-10-31 00:00:00 | 1) A HAZARDOUS MATERIALS KNOX-BOX | | | WILL BE REQUIRED. PLEASE SEE CITY | | | ORDINANCE 3206-99 FOR FURTHER DETAILS. | | | | | | 2) EXIT SIGN SYMBOL APPEARS IN THE | | | WRONG LOCATION FOR EXTERIOR DOOR OF | | | LAB 116. | | | | | | 3) PLEASE EXPLAIN PURPOSE OF HOLD-OPEN | | | DEVICES ON DOUBLE DOORS FOR MATERIALS | | | STORAGE ROOM 118. SHOULD THESE DOORS | | | REMAIN CLOSED DUE TO THE MATERIALS | | | BEING STORED WITHIN IT. | | | | | | 4) NO EXIT SIGNAGE OR EMERGENCY LIGHTING | | | SHOWN FOR THE MEZZANINE. | | | | | | 5) WHAT WILL THE FUME HOOD BE USED FOR. | | | | | | 6) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR FIRE ALARM SYSTEM. | | | | | | 7) NO FIRE SPRINKLER DRAWINGS PROVIDED | | | WITH PLANS. | | | | | | 8) BUILDING ADDRESS REQUIRED ON | | | PROPER ELEVATION. | | | | | | 9) PLEASE PROVIDE PRODUCT APPROVALS | | | FOR THE FIRE SHUTTERS ON PAGE A-6. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|