2003-10-31 00:00:001) A HAZARDOUS MATERIALS KNOX-BOX
 WILL BE REQUIRED. PLEASE SEE CITY
 ORDINANCE 3206-99 FOR FURTHER DETAILS.
  
 2) EXIT SIGN SYMBOL APPEARS IN THE
 WRONG LOCATION FOR EXTERIOR DOOR OF
 LAB 116.
  
 3) PLEASE EXPLAIN PURPOSE OF HOLD-OPEN
 DEVICES ON DOUBLE DOORS FOR MATERIALS
 STORAGE ROOM 118. SHOULD THESE DOORS
 REMAIN CLOSED DUE TO THE MATERIALS
 BEING STORED WITHIN IT.
  
 4) NO EXIT SIGNAGE OR EMERGENCY LIGHTING
 SHOWN FOR THE MEZZANINE.
  
 5) WHAT WILL THE FUME HOOD BE USED FOR.
  
 6) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM SYSTEM.
  
 7) NO FIRE SPRINKLER DRAWINGS PROVIDED
 WITH PLANS.
  
 8) BUILDING ADDRESS REQUIRED ON
 PROPER ELEVATION.
  
 9) PLEASE PROVIDE PRODUCT APPROVALS
 FOR THE FIRE SHUTTERS ON PAGE A-6.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910