| Plan Review Notes For Permit 03100570 |
| Permit Number |
03100570 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-10-16 00:00:00 | ************* UNSAT ****************** | | | | | | 1)NOTE: PLEASE CORRELATE PLANS AND | | | RISER/PANEL DIAGRAM. PLANS SHOW CIRCUITS | | | FOR A PANEL "H". PLEASE SEE RISER, SHOWS | | | WHAT APPEARS TO BE A PANEL "M"? | | | PLEASE CORRELATE. | | | | | | 2)NOTE: PLEASE CLARIFY LOCATION OF PANEL | | | "LA" AND PANEL "H/M" ON PLANS. PANEL LB | | | WAS LOCATED. | | | | | | 3)NOTE: PLEASE SEE 61G15-23.002 FOR ALL | | | REQ'D LICENSE INFORMATION ON TITLE BLOCK | | | FAC,FS 471. | | | THIS WOULD INCLUDE CA#'S. | | | PLEASE SEE THAT THIS REQ'D ON ALL SHEETS | | | FOR ALL TRADES EVEN A COMMENT IS NOT | | | MADE BY ADDTIONAL PLAN REVIEWERS. | | | | | | PLEASE SEE OTHER REVIEWERS COMMENTS,AS | | | THEY MAY HAVE AN AFFECT ON ELECTRICAL | | | PLANS. | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | INSERT NEW SHEETS FOR REVIEW AND STAMP- | | | -ING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | PLEASE SEE THAT WE ARE NOW UNDER THE | | | 2002 NEC AS OF 7/1/03 | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | 2003-10-15 00:00:00 | REVIEW IN PROGRESS, NOTES TO FOLLOW. |
|