| 2003-11-06 00:00:00 | BUILDING CHECKLIST: |
| | 1-ARCHITECT SEALING PLANS TO HAVE HIS |
| | NAME WRITTEN AS REQ'D BY CHAPTER |
| | 61G1-16.004. |
| | **ALSO, ARCHITECT TO DATE PLANS WHEN |
| | SEALING THEM. |
| | 2-DESIGN CRITERIA: SPECIFY ATTIC LIVE |
| | LOAD AS REQUIRED BY TABLE 1604.1 |
| | FBC 2001 FOR STORAGE OR NON-STORAGE. |
| | 3-REVISE ONE HR FIRE RATED GLASS BLOCK |
| | ASSEMBLY DETAIL. PROVIDE SPECIFIC UL |
| | ASSEMBLY LISTING TO BE USED AND REVISE |
| | DETAIL TO MATCH ULSPECIFICATIONS. |
| | **NOTE: 12"X12"X4" GLASS BLOCK DOESN'T |
| | MEET THE SPECS FOR ONE HR FIRE RATING. |
| | SEE UL LISTED ASSEMBLY. |
| | 4-SPECIFY SUPPORTS AND SPACING FOR WWM |
| | IN CONCRETE SLAB. SEE SEC. 1909.3 FBC |
| | 5-PROVIDE 2 COMPLETE SETS (SIGNED AND |
| | SEALED) OF TRUSS DRAWINGS REVIEWED BY |
| | ENGINEER OF RECORD. |
| | 6-SPECIFY SAFETY GLASS AT: A)BATHRM #2. |
| | B)ENTRY DOOR SIDELITE. |
| | C)GLASS BLOCK IF FACE THICKNESS IS LESS |
| | THAN 0.25". |
| | SECTION 2405.2 FBC 2001. |
| | 7-CLARIFY GARAGE DOOR FASTENER SPACING. |
| | SEE DETAIL B/4 AND NOTES ON DWG #2. |
| | ALSO, CLARIFY WHY ARE THERE MORE FASTE |
| | NERS AT HEADER THAN AT JAMBS IF GARAGE |
| | DOORS ARE TRANSFERRED TO THE JAMBS, |
| | NOT TO THE HEADER. SECTION 104.2.1.2 |
| | CITY AMENDMENTS TO FBC 2001. |
| | 8-PROVIDE DETAIL/SPECS FOR CEILING INSTA |
| | LATION AT FRONT AND REAR PORCHES. SEE |
| | ASTM C-926 AND ASTM C-1063 AND SPECIFY |
| | ALL MATERIALS AND FASTENERS. |
| | SEC. 2504.2 FBC 2001. |
| | 9-SPECIFY CALCULATED UPLIFT LOADS ON |
| | ROOF FRAMING PLANS. SEC. 104.2.1.2 |
| | CITY AMENDMENTS TO FBC 2001. |
| | 10-CLARIFY/REVISE DESIGN PRESSURES AT |
| | EXTERIOR OPENINGS. VALUES GIVEN DON'T |
| | CORRESPOND TO TABLES 1606.2A AND |
| | 1606.2E FBC 2001 ACCORDING TO LOCATION |
| | (END OR INTERIOR ZONE). ALSO, HOW COME |
| | LARGER OPENINGS WILL HAVE THE SAME |
| | PRESSURES AS SMALLER OPENINGS. SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | 11-STORM SHUTTERS: A)PROVIDE STATEWIDE |
| | PRODUCT APPROVAL AS OF OCT. 1ST. 2003. |
| | SEE ATTACHED QUESTIONS & ANSWERS COPY. |
| | B)PROVIDE KEY PLAN AND COMPLETE INSTALLA |
| | TION SCHEDULE. |
| | C)CLEARLY MARK ON DRAWINGS SPECIFIC |
| | MOUNTING CONDITIONS AND ANCHOR TYPE & |
| | SPACING TO BE USED ACCORDING TO THE |
| | DESIGN PRESSURES, EDGE DISTANCE, PANEL |
| | SPAN, CONNECTION TYPE AND STRUCTURE TO |
| | BE ATTACHED TO (MASONRY OR CONCRETE). |
| | |
| | 12-OWNER/AGENT AND PREPARER TO SIGN AND |
| | DATE ENERGY CALCULATIONS. |
| | 13-PROVIDE STATEWIDE PRODUCT APPROVALS |
| | FOR DOORS, WINDOWS, MULLIONS, ROOF |
| | REQUIRED AS OF OCT. 1ST 2003. SEE |
| | FLORIDA PRODUCT APPROVAL QUESTIONS AND |
| | ANSWERS COPY. ATTACHED. |
| | 14-SEE COMMENTS ON MARKED SET OF PLANS & |
| | RETURN REVIEWED SET AFTER CORRECTIONS |
| | ARE DONE TO ORIGINAL SET TO EXPEDITE |
| | REVIEW PROCESS WITHOUT HAVING TO GO |
| | OVER ALL PLANS AGAIN. |
| | 15-UPDATE INFORMATION ON SHEET 1. SEE |
| | COMMENTS ON PLAN. |
| | 16-REVISE/UPDATE TRUSS ANCHOR SCHEDULE |
| | AND ALL DETAILS THAT ARE AFFECTED BY |
| | SEC. 1609.4.3 FBC 2001 WHICH DOESN'T |
| | ALLOW ALLOWABLE STEEL STRESS TO BE |
| | INCREASED. PROVIDE CALCULATIONS FOR |
| | VALUES OTHER THAN THOSE PUBLISHED ON |
| | THE REVISED ANCHOR CATALOGUE. SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | B)SPECIFY SPECIFIC ANCHOR, STRAP SIZE TO |
| | PROPERLY CHECK LOADS. |
| | 17-NOTE #8 ON SHEET #2: CLARIFY WHY |
| | NAILING IS NOT REQUIRED AT EDGES. SEC. |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | 18-SHEET #4:A)SPECIFY ROOF TILE FASTENER |
| | SEC. 104.2.1.1 CITY AMENDMENTS TO FBC. |
| | B)REVISE BUCK DETAILS. SEE SECTION |
| | 1707.4.4.2 FBC 2001 FOR PROPER BUCK |
| | INSTALLATION. |
| | C)COMPLETE DOOR BUCK DETAIL. SHOW DOOR & |
| | SEE SEC. 1707.4.4.2 FBC 2001. |
| | D)CLARIFY DETAIL 5/4. HOW ARE 2 2X4'S |
| | FASTENED WITH 3" LONG TAPCON?. SEC. |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | E)STUCCO ON PLAYWOOD SHEATHING TO BE |
| | 7/8" MIN. SEE ASTM C-926. |
| | |
| | 19-SHEET #7: A)SPECIFY UPLIFT LOADS AT |
| | PORCH GIRDER TRUSS. SECTION 104.2.1.2 |
| | CITY AMENDMENTS TO FBC 2001. |
| | B)CLARIFY WHERE IS CONNECTOR EHUH 28-3 |
| | TAKEN FROM?. UNABLE TO FIND ON USP |
| | CATALOGUE 2003 (REVISED CATALOGUE). |