| Date |
Text |
| 2003-10-30 00:00:00 | DENIED |
| | |
| | 1) SUBMIT THE SUBSURFACE SOIL REPORT FOR |
| | THE PROJECT SIGNED AND SEALED BY THE |
| | SOIL ENGINEER. SEE FBC 1804.2.2 AS |
| | AMENDED BY THE CITY OF WPB. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. REQUIRED FOR EACH |
| | PERMIT. |
| | |
| | 3) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | REQUIRED FOR EACH PERMIT. |
| | |
| | 4) TWO COPIES OF A SIGNED AND SEALED |
| | SURVEY SHOWING THE LOCATION OF STRUCTURE |
| | IS REQUIRED FOR EACH SUBMITTAL. |
| | |
| | 5) ENERGY CALCULATIONS ARE REQUIRED TO |
| | BE SIGNED AND DATED BY THE OWNER/AGENT. |
| | THE ENERGY CALCS. SHOULD BE DONE AS |
| | WORST CASE. IF NOT EACH ONE WILL BE |
| | DIFFERENT BASED ON THE ORIENTATION OF |
| | THE STRUCTURE. IF WORST CASE IS |
| | SPECIFIED ON THE FORM THE SAME |
| | INFORMATION CAN BE SUBMITTED FOR EACH |
| | UNIT OF THE SAME MODEL. |
| | |
| | 6) REVISE THE BUCK ANCHORING SPECIFIED |
| | UNDER #1 OF RESIDENTIAL NOTES ON SHEET 2 |
| | TO CORRESPOND WITH THE BUCK DETAILS ON |
| | SHEET 4. |
| | |
| | 7) PLEASE CLARIFY IF THE SPACE BETWEEN |
| | THE ENTRY DOOR AND THE FIXED GLASS |
| | TRANSOM IS TO BE A LINTEL OR STRUCTURAL |
| | MULLION. |
| | |
| | 8) SPECIFY THE CEILING TYPE FOR THE |
| | FRONT AND REAR PORCHES ON THE PLANS. IF |
| | THEY ARE WIRE RIB LATH AND STUCCO, |
| | SPECIFY THAT RIB LATH WILL BE FASTENED |
| | AT EACH RIB (4"OC) WITH NAILS OR STAPLES |
| | THAT PROVIDE AT LEAST 1-3/4" PENETRATION |
| | INTO THE VERTICAL FRAMING MEMBERS. |
| | |
| | 9) PRODUCT APPROVALS SUBMITTED AFTER |
| | OCTOBER 1, 2003 ARE REQUIRED TO COMPLY |
| | WITH THE FLORIDA PRODUCT APPROVAL SYSTEM |
| | FOR INFORMATION SEE THE STATE WEB SITE |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET WHICH LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE (SEE SAMPLE ATTACHED). IF THE |
| | PRODUCT DOES NOT HAVE STATEWIDE APPROVAL |
| | SUBMIT AN APPLICATION FOR LOCAL PRODUCT |
| | APPROVAL PER RULE 9B-72. |
| | |
| | 10)INDICATE THE MOUNT TYPE AND ANCHOR |
| | TYPE THAT WILL BE USED FOR THE STORM |
| | PANELS. CIRCLE OR HIGHLIGHT THE |
| | APPROPRIATE ITEMS ON THE APPROVED STORM |
| | PANEL DRAWINGS. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |